c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 23 of 120
day1
2= working
day2
PT25 Friday schedule 1 0 2 OR
0= none
working day
1= working
day1
2= working
day2
PT26 Saturday schedule 0 0 2 OR
0= none
working day
1= working
day1
2= working
day2
PT27 Sunday schedule 0 0 2 OR
0= none
working day
1= working
day1
2= working
day2
Level
1
USER MENU
ModE
It sets the operating mode:
0: Cool, (Chiller/summer)
1: Heat (Heat pump/winter)
0 0 1 UT
Modifiable
only if the
units is a
chiller + heat
pump:
(PG00=2,4)
SPC1
It sets the value of the summer set
point (chiller)
8.5 PC21 PC22 °C UT
SPH1
It sets the value of the winter set
point (heat pump).
44.0 PC23 PC24 °C UT
PUC1
Offset for the summer set point by
digital input
2.0 -20.0 20.0 °C UT
PUH1
Offset for the winter set point by
digital input
-2.0 -20.0 20.0 °C UT
PSd1
It modifies the password at User
level.
0 -999 9999 UT
Level
2
MAINTENANCE MENU
OPERATION
PM00
It sets the maximum number of
operating hours of compressors.
When this limit is exceeded, the
connected alarm is triggered.
2000 0 9999 Hrs. x10 MA-F
PM01
PM02
PM03
PM04
PM05
PM06
It shows the number of operating
hours of compressors. One parameter
for each compressor.
0 0 9999
Hrs.
x10
MA-F
PM30
It sets the maximum number of
operating hours of pumps. When this
2000 0 9999 Hrs. x10 MA-F