EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 26 of 120
sensor
PM74
Calibration of leaving temperature
sensor circuit 1
0.0 -10.0 10.0 °C MA-C
PM75
Calibration of leaving temperature
sensor circuit 2
0.0 -10.0 10.0 °C MA-C
PM76
Calibration of source leaving
temperature sensor circuit 1
0.0 -10.0 10.0 °C MA-C
PM77
Calibration of source leaving
temperature sensor circuit 2
0.0 -10.0 10.0 °C MA-C
PM78
Calibration of coil temperature sensor
circuit 1
0.0 -10.0 10.0 °C MA-C
PM79
Calibration of coil temperature sensor
circuit 2
0.0 -10.0 10.0 °C MA-C
PM80
Calibration of discharge compressors
temperature sensor circuit 1
0.0 -10.0 10.0 °C MA-C
PM81
Calibration of discharge compressors
temperature sensor circuit 2
0.0 -10.0 10.0 °C MA-C
PM82
Calibration of remote
aux.temperature sensor
0.0 -10.0 10.0 °C MA-C
PM83
Calibration of condensing pressure
sensor circuit 1
0.0 -20.0 20.0 Bar MA-C
PM84
Calibration of condensing pressure
sensor circuit 2
0.0 -20.0 20.0 Bar MA-C
PM85
Calibration of evaporatorating
pressure sensor circuit 1
0.0 -20.0 20.0 Bar MA-C
PM86
Calibration of evaporatorating
pressure sensor circuit 2
0.0 -20.0 20.0 Bar MA-C
PM87
Calibration of unique pressure sensor
circuit 1
0.0 -20.0 20.0 Bar MA-C
PM88
Calibration of unique pressure sensor
circuit 2
0.0 -20.0 20.0 Bar MA-C
PSd2
It modifies the password at
Maintenance Operator level.
0 -999 9999 MA-F
Level
3
INSTALLATION MENU
COMPRESSORS
PC01
Rotation type used for compressor
management:
0: FIFO
1: LIFO
2: FIFO + hours
3: LIFO + hours
0 0 3 IS-C
PC02
Enabling mode of compressors in the
two circuits:
0: Circuit balancing
1: Circuit saturation
0 0 1 IS-C
Only on twin
circuits
PC04
Min. time for which the compressor
must remain ON, even if a shutdown
has been requested.
20 0 999 Sec. IS-C
PC05
Min. time for which the compressor
must remain OFF, even if a start-up
has been requested.
120 0 999 Sec. IS-C
PC06
Min. time which must elapse between
two start-ups of the same
360 0 999 Sec. IS-C