EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 33 of 120
with the compressor thermal alarm
PA42
It sets the type of reset for the
compressor thermal alarm
0: A - Automatic
1: M – Manual
M A (0) M (1) IS-S
PA50 Enable Source Flow alarm No (0) No (0) Yes (1) IS-S
Only for
Water-Water
unit
PA51
Source Flow alarm delay from
machine start-up
10 1 999 Sec. IS-S
Only for
Water-Water
unit
PA52
Source Flow alarm by-pass time
during normal operation
1 1 999 Sec. IS-S
Only for
Water-Water
unit
PA53
Minimum water valve opening to test
the flow of the heat source exchanger
5.0% 0.0% 100.0% % IS-S
Only for
Water-Water
unit
PA60
It enables the alarm connected with
operating hours of pumps
Yes (1) No (0) Yes (1) IS-S
PA61
It enables the alarm connected with
operating hours of source pumps
No (0) No (0) Yes (1) IS-S
Only for
Water-Water
unit
PA62
It sets the type of reset for the water
pump thermal alarm
0: Auto - Automatic
1: Manu - Manual
M A (0) M (1) IS-S
PA63
It sets the type of reset for the source
water pump thermal alarm
0: Auto - Automatic
1: Manu - Manual
M A (0) M (1) IS-S
Only for
Water-Water
unit
PA71
It sets the type of reset of high
pressure alarm restoration
0: Auto - Automatic
1: Manu - Manual
M A (0) M (1) IS-S
PA80
It enables the alarm connected with
operating hours of condensing fans
Yes (1) No (0) Yes (1) IS-S
PA81
It sets the triggering delay connected
with the condensing fan thermal
alarm
10 0 999 Sec. IS-S
PA82
It sets the type of reset for the
condensing fan thermal alarm
0: A - Automatic
1: M – Manual
M A (0) M (1) IS-S
PA85
Setpoint for the high temperature
discharge gas alarm of circuit 1
90.0 70.0 140.0 °C IS-S
PA86
Differential for the high temperature
discharge gas alarm of circuit 1
20.0 10.0 30.0 °C IS-S
PA87
It sets the triggering delay connected
with the high temperature discharge
gas
30 0 999 Sec. IS-S
PA88
It sets the type of reset for the high
temperature discharge gas
0: A - Automatic
1: M – Manual
M A (0) M (1) IS-S