7.3 DI Configuration(HB01-HB18 parameters)
Below is a table of values for configuring the positions of the digital inputs of the controller and of the expansion.
HB01-HB18 Parameters Digital Inputs
0 Disabled
1-2 Summer/Winter NC-NO
3-4 On/Off NC-NO
5-6 Set point change NC-NO
7-8 Heat sink exchanger flow meter NC-NO
9-10 Heat source exchanger flow meter NC-NO
11-12 Heat sink exchanger Heat pump 1 NC-NO
13-14 Heat sink exchanger Heat pump 2 NC-NO
15-16 Heat source exchanger Heat pump 1 NC-NO
17-18 Heat source exchanger Heat pump 2 NC-NO
19-20 Free Cooling external heater fan NC-NO
21-22 High pressure Circuit 1 NC-NO
23-24 Low pressure Circuit 1 NC-NO
25-26 Thermal compressor 1 NC-NO
27-28 Thermal compressor 2 NC-NO
29-30 Thermal compressor 3 NC-NO
31-32 Circuit1 heater fan NC-NO
33-34 High pressureCircuit 2 NC-NO
35-36 Low pressureCircuit 2 NC-NO
37-38 Thermal compressor 4 NC-NO
39-40 Thermal compressor 5 NC-NO
41-42 Thermal compressor 6 NC-NO
43-44 Circuit 2 heater fanNC-NO
7.4 AO Configuration (HC01-HC18 parameters)
Below is a table of values for configuring the positions of the analog outputs of the controller and of the expansion.
Parameters
Analog Outputs
HC07 HC08
HC09 HC10
HC11 HC12
0 0 0 Disabled
1 1 1 Free Cooling 3-way valve (0-10V)
2 2 2 Free Cooling external fan(0-10V)
3 3 3 Circuit 1 ventilation (0-10V)
4 4 4 Circuit 1 water valve (0-10V)
5 5 5 Circuit 2 ventilation (0-10V)
6 6 6 Circuit 2 water valve (0-10V)
7 - - Free Cooling external fan (PWM)
8 - - Circuit 1 ventilation(PWM)
9 - - Circuit 2 ventilation(PWM)
- 7 - Free Cooling external fan (4-20mA)
- 8 - Circuit 1 ventilation (4-20mA)
- 9 - Circuit 2 ventilation (4-20mA)