8 REGULATIONS
8.1 Machine Status
Several procedures exist for switching the unit ON and OFF:
1) Using the dedicated ON/OFF key (this function is enabled via parameter PH05).
Switching ON Press the dedicated key for about 2 seconds: if all other enabled functions are present, the machine switches
itself ON.Switching OFF – Press the dedicated key for about 2 seconds: the machine switches itself OFF.
2) Using the ON/OFF command from digital input (this function is enabled via parameter PH07).
Switching ON – Close the remote ON/OFF contact: if all other enabled functions are present, the machine switches itself ON.
Switching OFF If the remote ON/OFF contact reveals itself to be open, the machine switches itself “OFF from digital input”,
which is indicated by “OFF D”.
3) Using a supervisory protocol (this function is enabled via parameter PH09).
Switching ON – Activate via protocol the switching ON status: if all other enabled functions are present, the machine switches
itself ON.Switching OFF If the ON status is disabled via protocol, the machine switches itself “OFF by supervisory protocol”,
which is indicated by “OFF S”.
4) Using a schedule (this function is enabled via parameter PH16).
Switching ON – If the date and time of the RTC indicates an ON status: if all other enabled functions are present, the machine
switches itself ON.Switching OFF – If the date and time of the RTC indicates an OFF status; the machine switches itself OFF.
OFF statuses from digital input, supervisory protocol and schedule are only accessible if the machine has been enabled by key press.