EasyManua.ls Logo

Evco c-pro 3 micro CHIL Series - 8.16 Temperature Alarm Control; 8.17 Pressure Alarm Control

Evco c-pro 3 micro CHIL Series
222 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 73 of 120
8.16 Temperature Alarm Control
8.16.1 Low and high temperature alarm management
According to operating mode, a check is carried out on the exchanger inlet temperature, triggering an alarm where appropriate.
In winter operation (heat pump), if the temperature falls below a given threshold for a settable lapse of time, a “low
temperature” alarm is generated: AL01.
In summer operation (chiller), if the inlet temperature exceeds a given threshold for a settable lapse of time, a “high
temperature” alarm is generated: AL02
Via a configuration parameter, alarms can be set to be display-only alarms, or to stop the machine.
It is also possible to set a temperature-alarm inhibition delay from system start-up, so as to give the machine a chance to reach full
power.
PA05 = High-temperature alarm set point
PA06 = Low-temperature alarm set point
PA07 = Temperature alarm enable delay
PA08 = Temperature alarm management mode (display-only / machine stop)
PA09 = Temperature alarm differential
PA10 = System start-up alarm inhibition time.
These alarms are only detected when the machine is switched ON.
8.16.2 Management of primary exchanger efficiency alarm
If this alarm AL03 (and AL13 for Circuit # 2) is enabled (PA25 = 1), a check is made as to whether the difference between entering
and leaving chilled water temperatures at the primary exchanger, is below a Primary exchanger difference minimum threshold PA26 for
a By-pass time for primary exchanger efficiency alarm PA27.
This alarm is not managed during defrosting, if sensors are in alarm status and this alarm is a manual-reset alarm.
This alarm is only detected when the machine is switched ON.
8.17 Pressure Alarm Control
8.17.1 Management of high-pressure pressure-switch alarm
Via a digital input connected to an external pressure switch, it is possible to monitor an excess of maximum condensing pressure. The
high-pressure alarmAL11 (and AL12 for Circuit # 2) causes the immediate stopping of the refrigerating circuit, also shutting down any
compressors which may be ON, and inhibiting the start-up of others.
This alarm is only detected when the machine is switched ON.
This is a manual-reset alarm.
8.17.2 Management of high-pressure transducer alarm
If condensing pressure exceeds a given threshold, a high-pressure alarm AL31 (and AL32 for Circuit # 2) is generated. The alarm
causes the immediate stopping of the refrigerating circuit, also shutting down any compressors which may be ON, and inhibiting the
start-up of others.
This alarm is only detected when the machine is switched ON.
This is a manual-reset alarm and it can be reset if in the meantime pressure has fallen below the maximum threshold of a given
differential value.
PA21 = High-pressure alarm set point
PA22 = High-pressure alarm differential.
8.17.3 Management of low-pressure pressure-switch alarm (chiller mode)
Via a digital input connected to an external pressure switch, it is possible to monitor the presence of a minimum intake pressure in the
refrigerating circuit. The low-pressure alarmAL41 (and AL42 for Circuit # 2) causes the immediate stopping of the refrigerating circuit,
also shutting down any compressors which may be ON, and inhibiting the start-up of others.
At start-up of the first compressor, the alarm is delayed for a given interval, to enable the compressors to take the refrigerating circuit
to full pressure.
The alarm is initially auto-resetting, unless it exceeds a given number of events within one hour (PA14), in which case it becomes a
manual-reset alarm.

Related product manuals