8.18 Time schedule
The real time clock allows the operator to define a weekly schedule for the unit.
Two different daily schedules can be defined. Each daily schedule can have 2 zones with separate heating and cooling offset values.
Each day of the week can be assigned to daily schedule 1, daily schedule 2 or can be identified as none working day.
The parameters referred to this function are the following:
PARAMETERS FUNCTION
PT01 Working day 1 enable zone 1
PT02 Working day 1 zone 1 start time
PT03 Working day 1 zone 1 stop time
PT04 Working day 1 zone 1 cooling offset
PT05 Working day 1 zone 1 heating offset
PT06 Working day 1 enable zone 2
PT07 Working day 1 zone 2 start time
PT08 Working day 1 zone 2 stop time
PT09 Working day 1 zone 2 cooling offset
PT10 Working day 1 zone 2 heating offset
PT11 Working day 2 enable zone 1
PT12 Working day 2 zone 1 start time
PT13 Working day 2 zone 1 stop time
PT14 working day 2 zone 1 cooling offset
PT15 working day 2 zone 1 heating offset
PT16 working day 2 enable zone 2
PT17 working day 2 zone 2 start time
PT18 working day 2 zone 2 stop time
PT19 working day 2 zone 2 cooling offset
PT20 working day 2 zone 2 heating offset
PT21 Monday schedule
PT22 Tuesday schedule
PT23 Wednesday schedule
PT24 Thursday schedule
PT25 Friday schedule
PT26 Saturday schedule
PT27 Sunday schedule
PH16 Enable start-up/shutdown of the machine by the schedule