AC02 Operating hours compressor #2 Auto Display only
AC03 Operating hours compressor #3 Auto Display only
AC04 Operating hours compressor #4 Auto Display only
AC05 Operating hours compressor #5 Auto Display only
AC06 Operating hours compressor #6 Auto Display only
AP01 Operating hours pump #1 Auto Display only
AP02 Operating hours pump #2 Auto Display only
AP03 Operating hours source pump #1 Auto Display only
AP04 Operating hours source pump #2 Auto Display only
AF01 Operating hours fan Circuit #1 Auto Display only
AF02 Operating hours fan Circuit #2 Auto Display only
AL06 Source flow meter A/M
Compressors OFF
Pump ON for
T-secs.
Settable delay
In manual stop, pump OFF
AL83 Source anti-frost Circuit #1 Manu
Circuit compressors OFF and
Pump ON for T-secs.
AL84 Source anti-frost Circuit #2 Manu
Circuit compressors OFF and
Pump ON for T-secs.
ERTC RTC Alarm broken or discharged A/M Inhibits management of RTC -
EN01 Expansion communication alarm Auto Display only Settable delay
EVM1 EVCM Circuit #1 communication alarm Auto All circuit compressors OFF Settable delay
EVM2 EVCM Circuit #2 communication alarm Auto All circuit compressors OFF Settable delay
ES01 External ambient temperature probe Auto Inhibits functions using it
ES02 System input temperature probe (FC) Auto Inhibits functions using it
ES03
Remote aux. temperature probe aux
(accumulation tank)
Auto Inhibits functions using it
ES04 Heat sink exchanger input temperature probe Auto
Settable number of ON
compressors
Settable delay
ES05
Circuit 1 heat sink exchanger output temperature
probe
Auto
Settable number of ON
compressors
ES06
Circuit 1 heat source exchanger output
temperature probe
Auto Inhibits functions using it
ES07 Circuit 1coil temperature probe Auto Inhibits functions using it
ES08 Circuit 1 condenser pressure probe Auto Settable fan forcing
ES09 Circuit 1 evaporation pressure probe Auto Settable fan forcing
ES10 Circuit 1 single pressure probe Auto Settable fan forcing
ES11
Circuit 1 compressor discharge temperature
probe
Auto Inhibits functions using it
ES12 Circuit 1 compressor intake temperature probe Auto Inhibits functions using it
ES13
Circuit 2 heat sink exchanger output temperature
probe
Auto
Settable number of ON
compressors
ES14
Circuit 2 heat source exchanger output
temperature probe
Auto Inhibits functions using it
ES15 Circuit 2 coil temperature probe Auto Inhibits functions using it
ES16 Circuit 2 condenser probe Auto Settable fan forcing
ES17 Circuit 2 evaporation probe Auto Settable fan forcing
ES18 Circuit 2 single pressure probe Auto Settable fan forcing
ES19
Circuit 2 compressor discharge temperature
probe
Auto Inhibits functions using it
ES20 Circuit 2 compressor intake temperature probe Auto Inhibits functions using it
AHW1 Duplicate configuration of analog input Auto Display only
AHW2 Duplicate configuration of digital input Auto Display only
AF03 Operating hours fan free-cooling Auto Display only