EVCO S.p.A. c-pro 3 nano | Hardware Manual ver. 1.0 | Code 114CP3NE104
page 17 of 26
25
PAr
Parameters
AI 7
AI 7
ntC
NTC
type of probe analogue input 7
PtC = PTC
PTC
ntC = NTC
NTC
Pt10 = Pt 1000
PT1000
rES = electric heater reading
RESIST
nA = not available
nA
26
PAr
Parameters
-
not available for
c-pro 3 nano
basic
AI 8
AI 8
ntC
NTC
type of probe analogue input 8
PtC = PTC
PTC
ntC = NTC
NTC
Pt10 = Pt 1000
PT1000
rES = electric heater reading
RESIST
nA = not available
nA
27
PAr
Parameters
-
not available for
c-pro 3 nano
basic
AI 9
AI 9
ntC
NTC
type of probe analogue input 9
PtC = PTC
PTC
ntC = NTC
NTC
Pt10 = Pt 1000
PT1000
rES = electric heater reading
RESIST
nA = not available
nA
28
PAr
Parameters
Errt
Al Err Time
2 Analogue input alarm delay by lack of communication
0... 240 s
29
PAr
Parameters
AOiM
AO impulse
20 Phase cutting pulse duration 1... 50 ms/10
30
PAr
Parameters
AO 1
AO 1
010V
0-10V
type of signal analogue output 1
FAn = phase cutting
FAN
0-10 = 0-10 V
0-10 V
PUM = PWM
PWM
nA = not available
nA
31
PAr
Parameters
AO1F
Freq
1000
1000
PWM signal frequency analogue output 1 10... 2,000 Hz
32
PAr
Parameters
AO1d
Delay ph.
0 PWM signal shift analogue output 1 0... 50 ms/10
33
PAr
Parameters
AO 2
AO 2
010V
0-10V
type of signal analogue output 2
FAn = phase cutting
FAN
0-10 = 0-10 V
0-10 V
PUM = PWM
PWM
nA = not available
nA
34
PAr
Parameters
AO2F
Freq
1000
1000
PWM signal frequency analogue output 2 10... 2,000 Hz
35
PAr
Parameters
AO2d
Delay ph.
0 PWM signal shift analogue output 2 0... 50 ms/10