EasyManuals Logo

Evco EV3 MVC User Manual

Evco EV3 MVC
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 1.0 | Code 144EV3MVI104
page 62 of 72
S71 %
Return fan analogue output value
-1 = Disabled
RO
S72 %
Water valve analogue output value
-1 = Disabled
RO
S73 %
Mixing chamber damper analogue output value
-1 = Disabled
RO
S74 %
Heater analogue output value
-1 = Disabled
RO
S75 %
Heater TK/OC output value
-1 = Disabled
RO
S76
Supply fan digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S77
Return fan digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S78
Compressor digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S79
Reversing valve digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S80
Rotary recovery heat exchanger/bypass damper digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S81
External air damper digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S82
Open water valve digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S83
Close water valve digital output value
Disabled =-1
OFF = 0
ON =1
RO
S84
Step 1 heater digital output value
-1 = Disabled
0 = OFF
1 = ON
RO
S85
Step 2 heater digital output value
-1 = Disabled
0 = OFF
RO