EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 1.0 | Code 144EV3MVI104
page 67 of 72
EVD EXP
- REACH (EC) Regulation no. 1907/2006
- EN 60730-1
- IEC 60730-1
- R&TTE 1999/5/EC (only applicable for EVJ LCD)
EV3K11
EVJ LCD
Power supply
EV3 MVC
12 VAC (+10 -15 %), 50/60 Hz (±3 Hz), max. 7 VA not insulated
Protect the power supply with a 1 A-T 250 V fuse.
EVD MVC
EVD EXP
115... 230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 6 VA insulated
Protect the power supply with a 2 A-T 250 V fuse.
EV3K11
- 12 VAC (±15 %), 50/60 Hz (±3 Hz), max. 5 VA not insulated
- 12 VDC (±15%), max. 5 W not insulated
Protect the power supply with a 1 A-T 250 V fuse
EVJ LCD
- 12 VAC (±15 %), 50/60 Hz (±3 Hz), max. 10 VA not insulated
- 12 VDC (±15%), max. 10 W not insulated
Rated impulse-withstand
voltage
EV3 MVC
4 KV
EVD MVC
EVD EXP
EV3K11
EVJ LCD
Over-voltage category
EV3 MVC III
EVD MVC
EVD EXP
II
EV3K11 Not applicable
EVJ LCD III