EasyManua.ls Logo

Evco EVJ LCD - Page 58

Evco EVJ LCD
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 2.2c | Code 1443DMVCI224
page 58 of 74
Label Visibility default min max UM description
S16 U
Temperature regulation mode
0: Cold
1: Hot
2: Auto+Cold
3: Auto+Hot
S17 S 0 2
Heating/Cooling mode setting
0: Cold
1: Hot
2: Auto
S18 U °C-°F Changeover probe value
S19 U
°C-°F Room probe value
S20 U
°C-°F External probe value
S21 U
°C-°F Return air humidity probe value
STem Temperature regulation
S22 U -10.0 100.0 °C-°F Temperature setpoint
S23 S
Temperature regulation type
0: Disabled
1: Follow-on regulation
2: Regulation on room temperature
3: Regulation on supply temperature
4: Forced by DI
S24 S °C-°F Regulation probe
S25 S °C-°F Temperature setpoint in use
S26 S
First coil type
0: Not available
1: Thermodynamic
2: 3-point, water
3: Modulating, water
4: ON-OFF, water
5: 2-step, electric
6: Modulating, electric
7: ON-OFF, electric
255: Not configured
S27 S
2nd coil type
0: Not available
1: ---
2: 3-point, water
3: Modulating, water
4: ON-OFF, water
5: 2-step, electric
6: Modulating, electric
7: ON-OFF, electric
255: Not configured
S28 S
Thermodynamic coil operating mode
0: OFF
1: ON
S29 S
Water coil 1 operating mode
0: OFF
1: ON
S30 S % Coil 1 valve opening
S31 S
Water coil 2 operating mode
0: OFF
1: ON
S32 S % Coil 2 valve opening

Table of Contents

Other manuals for Evco EVJ LCD

Related product manuals