EVCO S.p.A. EVJ800 | Installer manual ver. 1.0 | Code 144J800E104
page 32 of 48
PAR. DEFAULT
MIN. MAX. U.M. COMPRESSOR PROTECTION
C0 0 0 240 min
Minimum time between restoration of power supply after a
power failure occurring during an operating cycle and
compressor switch-on
C1 5 0 240 min Minimum time between two consecutive compressor switch-ons
C2 3 0 240 min
Minimum time between compressor switch-off and subsequent
switch-on
C3 0 0 240 s Minimum compressor-on time
C4 10 0 240 min
Compressor-off time during cabinet probe error (“CABINET
PROBEcode) occurring during conservation after blast chilling
and blast freezing;
see also parameters C5 and C9
C5 10 0 240 min
Compressor-on time during cabinet probe error (“CABINET
PROBE” code) occurring during conservation after blast
chilling;
see also parameter C4
C6 80 0 199 °C
Condenser temperature above which the condenser overheating
alarm is activated (“COND OVERHEATING code)
C7 90 0 199 °C
Condenser temperature above which the compressor locked
alarm is activated (“COMP LOCKEDcode), once the time set
for C8 has elapsed
C8 1 0 15 min
Activation delay of the compressor locked alarm (“COMP
LOCKED” code) due to threshold C7 exceeded
C9 30 0 240 min
Compressor-on time during cabinet probe error (“CABINET
PROBE code) occurring during conservation after blast
freezing;
see also parameter C4
PAR. DEFAULT
MIN. MAX. U.M. DEFROST
d0 8 0 99 h
Defrost interval
0 = defrosting during conservation is never activated
d1 1 0 3 - - - -
Type of defrost
0 = electrical (during defrosting the compressor is switched
off, the defrost output is activated and the evaporator
fan switched off)
1 = hot gas (during defrosting the compressor is switched
on, the defrost output is activated and the evaporator
fan is switched off)
2 = air (during defrosting the compressor is switched off and
the defrost output is activated. The evaporator fan is
switched on, regardless of the door status, or regardless
of the status of the door switch input)
3 = air with door open (during defrosting the compressor is
switched off and the defrost output is activated. The
evaporator fan is switched on, provided the door is open
or provided the door switch input is on and that
parameter i0 is set to a value other than 0)
d2 2 -50 99 °C
Evaporator temperature to end defrosting;
see also parameter d3