6.0 STARTUP AND SHUTDOWN PROCEDURES
6.1 Startup
After the unit is installed, the AC Input and Output wires landed and the batteries
are installed and wired per Sections 3 - 5, the unit is ready to be started up.
Ensure that the incoming AC voltage is reaching the unit by turning on all feed circuit
breakers. Once AC input is verified, simply turn on the System ON/OFF switch. The
unit will go through a series of diagnostics to verify proper connections and then will
go into the charge mode. The unit is now on-line and ready. Verify that all load
connections are operating within the specifications of the unit by measuring AC
currents on both the incoming line and outgoing load and measure all neutral
currents to ensure line and neutral currents are the same.
Press the Test button on the front panel to verify that all loads are operational and
ensure there are no overloads by measuring all the load currents.
If at any time you have questions – please consult the
factory
6.2 Shutdown
To completely shut the system down, switch the System ON/OFF switch to the OFF
position. If the unit is shut down for a long duration, please see Battery Storage
Section 2.2 to ensure that the batteries are not damaged from the effects of self-
discharge and high ambient temperatures.