12.0 WEB INTERFACE
The LM/LMOPT Series Emergency Lighting Inverter comes standard with
capability to connect to the web for access to all the system logs and
programmable features. To logon to the LM/LMOPT series, simply go to
Evenlite.com and click on the Inverter Monitoring link under the Resources
drop-down menu and follow the User Setup instructions below.
12.2 User Setup:
User Account set up requires a valid Central Inverter System serial
number to setup
up an account. With a verification of a valid serial number the following
information is required for the user to finish setting up the account:
Customer Name, User Name, Password, Address (up to 2 lines), City, State,
Country,
Phone1, Phone2 and Email address.
• This information is required for the Factory to Verify and
Authenticate the account. If account information is not valid, the
factory will remove account and deny access to machines.
Once the user has gone through this account setup process, they can
access critical information on their system by logging into their account and
clicking on the Control Panel icon for their machine.
Control Panel (System Home) Page
The Control Panel acts as the Systems Home Page. From this page, it is
possible to see several critical functions listed below plus several icons will
link the user to many more features.
Meter Functions – Input Voltage, Output Voltage, Output Current, Output
VA, System Battery Voltage, Battery Current (charging and discharging),
Battery Power, System Temperature, System Days, Inverter Minutes and
System Events.
Also included in the Control Panel is the System Status and include
indicators for Battery Charging, Inverter Power On, AC Present, System
Ready, and Switched Load Energized. The Alarm Summary indicator and
critical alarms indicators include Unit in Bypass, Circuit Breaker Trip, Startup
Fault, Charger Fault and Inverter Fault.
A System Test can be initiated by an icon located on the Control Panel.
Immediately after pressing this Icon, the system will perform a system test
and when complete will record test parameters in the Test Log. Please see
System Logs for details.
From the Control Panel Page the user has access to several links and include
User Setup, Alarms, Charts and Graphs and System Logs. Just click on the
icons on the home page to access these features.
LM/LMOPT SERIES | 45