8.0 Specifications
Input
Voltage
Current
Frequency
Protection
Power Factor
Output
Voltage
Current
Frequency
Overload
Transfer Time
Output
Distortion Crest
Factor Load
Power Factor
Output Types
Battery
Type
Charger
Recharge Time
Protection
Runtime
DC Voltage
DC Current
Environmental
Operating Temp
Storage Temp
Relative Humidity
Physical
Cabinet
Cooling
Size/Weight
Model and Voltage Dependent (Tables 8.1 through 8.4)
Model and Voltage Dependent (Tables 8.1 through 8.4)
60Hz +/- 2 Hz
Input Circuit Breaker standard
0.5 lead to 0.5 lag
Model and Voltage Dependent (Tables 8.1 through 8.4)
Model and Voltage Dependent (Tables 8.1 through 8.4)
60Hz +/- 0.02 Hz crystal controlled during emergency mode
110 percent will generate overload fault
125% will generate overload shutdown
2mS standard (User programmable to 50mS)
Less than 3% THD
4X minimum on all models
0.5 lead to 0.5 lag
1x Normally-On Standard – Normally-Off/Switched optional
Premium Long Life Valve-Regulated Lead Acid (VRLA)
3 rate with Temperature Compensation
24 Hour recharge standard
Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC
Automatic restart upon utility return
90 Minutes at 25 °C
Model and Voltage Dependent (Tables 8.1 through 8.3)
Model and Voltage Dependent (Tables 8.1 through 8.3)
20 to 30 °C
-20 to 70 °C (Electronics)
0 to 40 °C (Batteries)
<95 % (non-condensing)
NEMA Type 1 enclosure, 14 AWG powder painted CRS
Natural Convection – No fans during float charge
Forced Convection – Fans used during Inverter Mode of
operation Model and Voltage Dependent (Tables 8.1 through
8.3)
LM/LMOPT SERIES | 29