10.11 Test Log
Identical to the Event Log with the exception that the Test Log is only
stored when a system test is either:
a) initiated from either a manual process of the User pressing the Test
Button on the front panel keypad or,
b) when the system is instructed by the automatic monthly or yearly test.
10.12 Alarm Log
In the event an alarm occurs from one of many that the system can
produce, this alarm is immediately stored into memory. The alarm log has a
record of any and all alarms the system has experienced and is valuable for
troubleshooting and detecting issues. The Alarm Log is stored in a First in –
First out process just like the other logs and has the capability of storing up to
1000 alarms.
10.13 User Menu
From the Scrolling Home Pages, press Enter Key and down arrow to select
User Menu and press Enter to get to the password entry screen. The User
Password is 4 keystrokes - Left Key, Right Key, Left Key, and Right Key.
Upon successful password keystrokes, the User Menu is accessible and now
several alarms can be turned on/off and threshold levels for these alarms can
be changed. If the password keystroke was not successful, the Enter
Password will be prompted again and the user has the option of going back
with the left key to try again.
Date and Time
The date and time is preset from the Factory (East Coast Time), user
adjustable and battery backed up. The Date and Time are extremely accurate
and have a couple second per year gain/loss accuracy. All Test, Event and
Alarm Logs are time stamped from the machines date and time settings.
Furthermore, all Month and Year Tests are synchronized to the machine’s
date and time settings so it is imperative that the correct date and time are
set. Daylight savings time is not compensated for so in the event your area
observes daylight savings time, please change the machines time for most
accurate settings.
Month Test
Per the NFPA and UL requirements, a system test of the Emergency
Lighting equipment should be performed once per month. Which Day of the
month and what time of day are fully adjustable. Factory default is First Day
of month at 8:30 AM the test will be performed.
Year Test
In addition to the Month Test requirements of the NFPA and UL, it is
mandated that a 90-minute discharge be performed once per year. The
Month, Day and Time of this test is fully adjustable and the Factory default
for this test is off. If the Yearly test is enabled, the system will undergo a full
90-minute discharge test at the time and date determined by the settings.
40 | INSTALLATION / OPERATION MANUAL