CONFIGURATION PARAMETERS
-Put the display in OFF, press for 5 seconds the UP and DOWN buttons.
The display DIS1 shows the first parameter (the first label is PA: Password) The display DIS2
shows the parameters value.
Scroll the parameters list with the UP
and DOWN buttons.
Edit each parameters with the PROGRAM button, the LED associated with the key lights.
Change the value with the UP and DOWN buttons, confirm with the PROGRAM
buttons.
GET BACK TO THE OFF status pressing the UP and DOWN buttons for 5 seconds
or do not operate for 15 seconds.
PARAMETERS
LABEL DESCRIPTION MIN MAX DEFAULT U.M.
Temperatures
P0
Selects the measuring units for temperature
0 1 1 -1 = Celsius
0 = Fahrenheit
P1 Cell probe offset -10 10 0 °C
P2 Evaporator probe offset -10 10 0 °C
P3 Needle probe offset -10 10 0 °C
Adjustment Setpoint
P4 Blast chilling Cell Temperature Setpoint -40 99 -2 °C
P5 Cell Temperature Setpoint for Freezing -40 99 -40 °C
P6 Cell Temperature Setpoint for rst Hard Cycle phase -40 P4 -20 °C
P7 Cell Setpoint for Positive storage -40 99 3 °C
P8 Cell Setpoint for Negative storage -40 99 -20 °C
P9 Adjustment hysteresis 1 15 2 °C
P10 Needle Probe Temperature for end of Blast chilling -40 99 3 °C
P11 Needle Probe Temperature for end of Freezing -40 99 -18 °C
P12 Needle Probe Temperature pin for End of rst Hard cycle P10 99 15 °C
P13 Needle Probe Temperature Threshold for start of Decrease in time -40 99 65 °C
Needle probe insertion
P14
Temperature Difference between Needle probe and Cell for ins.
Needle probe
0 99 0 °C
P15 Needle probe Insertion Differential Test duration 1 99 60 Sec
Cycles Duration
P16 Temperature Cycle Duration 1 400 90 Min
P17 Freezing Cycle Duration 1 400 240 Min
P18 Duration of First Hard phase for Time Cycle 1 P16 20 Min
Compressor safety times
P19 Compressor Start Delay from Power On 0 99 0 Min
P20 Minimum time between two compressor starts 0 99 0 Min