EasyManua.ls Logo

Exodraft MEC24 - Page 11

Exodraft MEC24
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Interlock with dry set of contacts
Figure 9 shows how a dry set of contacts is connected to the MEC24:
y Connect the power supply to terminals 1, 2 and 3.
y Connection to the appliance:
Connect the dry set of contacts to terminals 12 and 13.
Connect the start signal to the burner to terminals 14 and 15.
y To connect the chimney fan:
If using a 1x120V chimney fan, connect it to terminals 4, 5 and 6. Refer to the fans Installation Manual.
If using a 3-phase fan and VFD, connect the VFD to terminals 20 and 21 as shown in Fig. 10 and 11. DO NOT con-
nect the fan directly to the MEC24 control.
Connect the XTP transducer to terminals 22, 23 and 24
XTP2
COM Vout Vin
Connection to 120 V Fan - Intermittent Operation
1 x 120V AC
Fig. 9
11
3120066 MEC24 US 20210325