Connection diagrams
10.
358
Ref.1912
DDS
HARDWARE
· 350 ·
Diagram for general connection to mains
F. H10/23
ACD/SCD compact drive, SERCOS. Diagram for general connection to mains.
PE
- S1
MECHANICAL
MAIN SWITCH
- F1
- F2
- F3
MAIN FILTER 42A-A
L1
L1L2
L3
3x 200-240 VAC
2x 200-240 VAC
L1
CONTACTOR
- KM1
L2
- Q1
DIFFERENTIAL
BREAKER
WARNING.
When using an isolating transformer, the secondary must be
connected in star and its middle point must be connected to GND.
POWER MAINS
IT A MUST TO USE FUSES
TO THE X1
CONNECTOR
ACD/SCD COMPACT
DRIVES
TO THE POWER CONNECTOR
ACD/SCD COMPACT DRIVES
L2
L3
N
R
S
T
3x 200-240 VAC
48 ... 62 Hz
PE
- S1
MECHANICAL
MAIN SWITCH
- F1
- F2
- F3
MAIN FILTER 42A-A
L1
L1L2
L3
3x 400-460 VAC
2x 400-460 VAC
L1
CONTACTOR
- KM1
L2
- Q1
DIFFERENTIAL
BREAKER
WARNING.
When using an isolating transformer, the secondary must be
connected in star and its middle point must be connected to GND.
POWER MAINS
IT A MUST TO USE FUSES
TO THE X1
CONNECTOR
ACD/SCD COMPACT
DRIVES
TO THE POWER CONNECTOR
ACD/SCD COMPACT DRIVES
L2
L3
N
RST
3x 400-460 VAC
48 ... 62 Hz
Line voltage: 400 (1-10 %) V AC / 460 (1+10 %) V AC
Line frequency: 48 ... 62 Hz
Line voltage: 200 (1-10 %) V AC / 240 (1+10 %) V AC
Line frequency: 48 ... 62 Hz
Note.
Observe that having the main key -S1 closed, although the power contactor - KM1 is open, the internal
24 auxiliary power supply of the unit remains connected through its connector X1 to feed the control circuits of
the drive.