CONNECTIONS SCHEAMTIC
24
The vitro-ceramic hotplate is supplied with a power cable
(N2GMH2G types) prepared for 220 to 240V AC.
If the type of connections to which the hotplate is to be installed is other than
220 to 240 V AC remove the cable and make the connection according to the
adjacent drawings. (The cable must support temperatures of up to 120ºC).
The hotplate must be connected to the mains with a plug that meets the EEC
7 publication or with a multi-pole switch with a distance between the open
contacts of a least 3mm.
Total power
Hotplate: 60 cms., 6,3kW
This device conforms to European dirctives 73/23/CEE and 89/336/CEE
60 cms 220...240V~ 27,5 A 32 A 220...240V~ 14 A 16 A
Voltage Int.nominal Protection
by phases
Voltage Int.nominal Protection
por fases
PLATE
Three phase
60 cms 380...400V~ 11 A 12 A 380...400V~ 16 A 20 A
Voltage Int.nominal Protection
by phases
Voltage Int.nominal Protection
by phases
PLATE
Three phase