Advanced Function Instruction
7-11
FUN32
ADCNV
CONVERTING THE RAW VALUE OF 420MA ANALOG INPUT
ADCNV
FUN32
ADCNV
Pl :
N :
EN
Ladder symbol
32.ADCNV
S :
D :
F/T
Operation Control
14/12 - Bit Selection
HR IR ROR DR K
Range
Ope-
rand
R0
R3839
R3840
R3903
R5000
R8071
D0
D4095
Pl 0~1
S
N 1~64
D *
Pl0, the polarity setting of analog input module is at unipolar
position
1, the polarity setting of analog input module is at bipolar
position
SStarting address of source registers
NQuantity of conversion (In Word)
DStarting address of destination registers
S, N, D may associate with VZP0~P9 index register to serve
the indirect addressing application.
When the analog input is 420mA, the analog input module is one of the solution to get this kind of signal,
but the input span of the analog input module is 020mA (Setting at 10VUnipolar), however there will exist
the offset of the raw reading value; this instruction is applied to eliminate the offset and convert the raw
reading value into the range of 04095(12-bit) or 016383(14-bit), it is more convenient for following
operation.
When execution control "EN"=1, it will execute the conversion starting from S, length by N, and then store
the results into the D registers.
This instruction will not act if invalid length of N.
When the inputF/T=0, it assigns the 12-bit analog input module; whileF/T=1, it assigns the 14-bit
analog input module.
Example
M0
32.ADSNV
EN
N :
D :
S :
F/T
P1 :
0
R3840
R500
6
DescriptionWhen M0 is ON, it will perfom 6 points of conversion starting from R3840, where the offset of 4
20mA raw reading value will be eliminated, and the corresponding value 04095 will be stored into
R500R505.
S D
R3840
1229
R500
0
(4 mA)
R3841 409 R501 2047 (12 mA)
R3842 2047 R502 4095 (20 mA)
R3843
2048
R503 0 (0 mA)
R3844
2048
R504 0 (0 mA)
R3845
2048
Ö
R505 0 (0 mA)