B. Class B, Style 4 Wiring Instructions
Remove the electronic end of line device from Terminals 1 and 4, 5, or 8, then install it in parallel within
or after the last device on the circuit.
Be sure to observe polarity.
Connect field wiring to the addressable initiating/control device as shown in Figure 4.
Maximum allowable resistance in the field wiring is 40 ohms per circuit including sub-loops and remote zone
modules.
Maximum capacitance 0.2 uf.
3.2 Ratings for IDU Signaling Line Circuits
Operating voltage 24 VDC (nominal)
Supervisory current 0.065 amp.
Alarm Current 0.085 amp.
Short circuit 0.75 amp. max.
Line resistance 40 ohms max.
Line capacitance 0.2 uf. max.
Unshielded, untwisted wire
Power limited
Supervised
End of Line device : P/N 4700-0508
5 68
7
OR
EOL-E
CPM
RZM
SLM
RIM-U
1
(+)
(+)
2
-
4
-(-)
(-)
3
Figure 3 Style 4 SLC Wiring
(-)
7
(+)
6
-
8
OR
5
RIM-U
SLM
RZM
301-ID
CPM
EOL-E
1
(+)
2
-
4
3
(-)
Figure 4 Style 6 SLC Wiring
NOTE: Only FC-ID, FCID-X approved modules listed in Section 1.2 can be used on the signaling line
circuits.
9 of 12 9000-0437