BLUEHELIX TECH RRT 24 H
168 EN
cod. 3541C662 - Rev. 00 - 09/2020
Accessing the electrical terminal block and fuse
Remove the front panel ( *** 'Opening the front panel' on page 189 ***) to access the terminal block (M) and fuse (F) by
proceeding as follows (fig. 20 and fig. 21). The terminals indicated in fig. 21 must be with voltage-free contacts
(not 230V). The arrangement of the terminals for the various connections is also given in the wiring diagram in fig. 58.
Variable output relay LC32 card (optional - 043011X0)
The variable output relay LC32 consists of a small card with a changeover of free contacts (closed means contact bet-
ween C and NO). Operation is managed by the software.
For installation, carefully follow the instructions provided in the kit package and on the wiring diagram of fig. 58.
To use the desired function, refer to the table 2.
Table 2- Settings LC32
fig. 20
fig. 21
Parameter b07 Function LC32 Action LC32
0 Manages a secondary gas valve (default)
The contacts are closed when the gas valve (in the boiler)
is powered
1 Use as an alarm output (warning light comes on)
The contacts are closed when there is an error condition
(generic)
2 Manages a water loading valve
The contacts are closed until the water pressure in the hea-
ting circuit is restored to the normal level (after manual or
automatic topping up)
3
Manages a solar 3-way valve The contacts are closed when the DHW mode is active
Manages a Legionella pump (only with b01=2)
The contacts are closed when the Legionella protection is
running
4 Manages a second heating pump The contacts are closed when the heating mode is active
5 Use as an alarm output (warning light goes off)
The contacts are opened when there is an error condition
(generic)
6 Indicates ignition of the burner The contacts are closed when the flame is present
7 Manages the trap heater
The contacts are closed when the frost protection mode is
active
F
M

Table of Contents

Other manuals for Ferroli BLUEHELIX TECH RRT 24 H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ferroli BLUEHELIX TECH RRT 24 H and is the answer not in the manual?

Ferroli BLUEHELIX TECH RRT 24 H Specifications

General IconGeneral
BrandFerroli
ModelBLUEHELIX TECH RRT 24 H
CategoryHeater
LanguageEnglish

Related product manuals