SERIES 2000 COMMUNICATIONS MANUAL 11
M41 Issue 1.1
The instrument would respond
*03C-0100<CR>
Note that the data field is padded out to 4 characters in both the query and response
messages.
3.14.2 Data field type 2.
This data field type is reserved for the controller status obtained by reading parameter L.
The instrument will respond with:
*NNLABCD<CR>
Where
NN
is the instrument address.
A
= Digital inputs = 0 Both off or unused
= 1 Input 1 on, 2 off or unused
= 2 Input 2 on, 1 off or unused
= 3 Both digital inputs are on.
B
= alarm condition = 0 Both alarms off
= 1 Alarm 1 on, alarm 2 off
= 2 Alarm 2 on, alarm 1 off
= 3 Both alarm 1 and 2 are on
C
= Tuner status = 0 pretune and atune are off
= 1 pretune is on, atune is off
= 2 atune is on, pretune is off
= 3 pretune and atune are on
D
= Auto/Man = 0 Automatic
= 1 Manual
3.14.3 Data field type 3
This data type is reserved for the instrument type code. The instrument type code may be
read from the controller by reading parameter code Q. The controller will respond with;
*NNQABCD<CR>
Where
A
= Input 2 = 0 Controller with remote setpoint
= 1 Controller without remote setpoint
= 3 Programmer/Controller
BC
= Input = 00 Type S, degrees C
type = 01 Type R, degrees C
= 02 Type J, degrees C
= 03 Type K, degrees C
= 04 Type T, degrees C
= 05 Type E, degrees C
= 06 Type B, degrees C