1. WARNING
TO DO:
● Please install the unit in compliance with local CODES, regulations and standards;
● Please use a solid base, such as 2 pieces of 16” x 16” x 4” concrete blocks or an equipment
base of 16” x 32 inches minimum size.
● Confirm power voltage and frequency; 110-125 volts, 60 Hz. 20 Amps.
● If the heater is within 50 feet of the breaker box, use 12 AWG gauge wire (12-2+ Ground) and
20 Amp breaker on a GFCI protected outlet.
● If the heater is 50-150 feet from the breaker box, use 10 AWG wire (10-2+Ground) and 20
Amps GFCI breaker.
● The heater must be BONDED to a ground rod, using #8 AWG bare copper wire.
● An external timer can be used, be sure it I an outdoor Appliance type, minimum 15 amps
Inductive.
● 1 1/2” schedule 40 PVC OR 1 ½” or 1 ¼” corrugated filter connection hoses OR 1.5” Intex
hoses must be used to connect plumbing.
● WATER AND ELECTRICITY DON’T MIX. PLEASE USE ALL PRECAUTIONS.
● This heater is made of mostly metal alloys and may have sharp edges. Please use gloves
while handling it.
● Keep a minimum of 6 feet distance between the heater and the pool wall.
● Fibropool FH135 is weatherproof and designed to be outdoors, but is not splash-proof. Choose
a location away from splashing from the pool.
NOT TO DO:
● Do NOT install this heater where there may be flammable gas.
● Do NOT install this heater in an enclosed room. Without adequate air supply, performance will
be severely limited. If the unit is installed in a closed area or limited space, please consider the
size of room and ventilation to prevent suffocation caused by refrigerant leakage.
● Do NOT try to lift the unit by yourself. The FH135 weighs about 100 lbs. It is a 2 person
handling size and weight.
● Do NOT install below eaves of the roof, where water pours onto it.
● DO NOT SHORTCUT ANY SAFETY PROCEDURES.