Installation Instructions
WARNING: Installation must be performed by a qualified person
This section is provided for information purposes only and may vary depending on your
location, regulations, and available space for installation
1. Pre-Requirements
Required equipment for installation of heat pump:
Suitable power outlet, 110-125 volts, GFCI protected outlet.
PVC pipe and fittings OR Corrugated filter connection hoses and necessary adapters, Pipe
cleaner/ primer, Medium Bodied Glue
Electrical tools, and a multi-meter
An equipment pad, 16” x 32” x 4” thick or 2 pieces of concrete blocks, 16 x 16 x 4 inches each
2. Location
Please consider the following when choosing a location for the heat pump:
1. Make sure the heater is not directly below roof drains, such as a gutter drain, or eaves.
2. Be sure that the heater does not submerge in water in heavy rain.
3. Be sure to install the drain adapters into the heater and attach the hose to direct the
condensation water. Heater will produce gallons of water from condensation daily.
4. Confirm the unit is in well-ventilated conditions and that the fan discharge grill vent is not
blocked (fan blows outwards.)
5. Keep at least 12 inches of clearance on the two short sides and the long radiator side.
6. Keep at least 3 feet of clearance on the fan side of the heater.
7. Keep the unit as far as possible out of the reach of children and within 25 feet of the pool.