44 MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Operating Instructions Operation
4.4.1 Fire Alarm Response
The control panel will, upon detection of an alarm condition, cause the following:
Latch the alarm condition - requires panel reset to clear alarm condition
Blink the Zone Alarm LED one second On and one second Off
Turn on remote annunciator alarm LED and piezo sounder
Turn the Notification Appliance Circuit(s) on
Turn the FACP piezo sounder on steady
Turn on the alarm relay
Start the Silence Inhibit, Auto-silence and Trouble Reminder functions if enabled
4.4.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system reset button has
been pressed (pull stations have been reset, smoke detectors have reset and no smoke is present,
waterflow has stopped). The control panel will perform the following upon restoral of all active
alarms:
Turn off the FACP Zone Alarm LED
Turn off remote annunciator alarm LED and piezo sounder
Turn off the Notification Appliance Circuit(s)
Turn off the FACP piezo sounder
Turn off the alarm relay
•i
3
smoke detectors will be polled for maintenance and freeze conditions on initial entry into
Normal mode. Thereafter, each device will be polled every hour for freeze and every four
hours for maintenance conditions
4.4.3 System Supervisory Condition Response
Zones can be programmed for supervisory in applications where a waterflow sensing device has
been employed and a sprinkler tamper switch is to be monitored. An I
3
detector in a ‘freeze’
condition (detected abnormally low ambient temperature) will also generate a supervisory
condition on its alarm zone (refer to the I
3
specification sheet for temperature threshold). Any
supervisory condition will cause the control panel to perform the following functions:
Blink the FACP Zone Supervisory LED ½ second On and ½ second Off
Pulse the piezo sounder ½ second On and ½ second Off
Turn on the supervisory relay (MS-4 only)
4.4.4 System Supervisory Restoral Response
When the supervisory condition has been cleared, the control panel will perform the following:
Turn off the FACP Zone Supervisory LED
Turn off the piezo sounder
Turn off the supervisory relay (MS-4 only)
4.4.5 Trouble Condition Response
The control panel, upon detection of one or more trouble conditions, well perform the following:
Blink the FACP System Trouble LED one second On and one second Off
Blink the FACP Zone Trouble LED one second On and one second Off
Turn on remote annunciator Trouble LED and pulse the piezo sounder

Table of Contents

Other manuals for Fire-Lite MS-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite MS-2 and is the answer not in the manual?

Fire-Lite MS-2 Specifications

General IconGeneral
BrandFire-Lite
ModelMS-2
CategoryControl Panel
LanguageEnglish

Related product manuals