MR95 Series
11
TYPE MR95LD REGULATOR (ALSO TYPICAL OF TYPE MR95HD)
Figure 3. Differential Pressure Regulator Installation Schematics
Installation
WARNING
!
Personal injury or system damage 
may result if this regulator is installed, 
without appropriate overpressure 
protection, where service conditions 
could exceed the limits given in the 
Specications section and/or regulator 
nameplate. Refer to Overpressure 
Protection section for recommendations 
on how to prevent service conditions 
from exceeding those limits.
Additionally, physical damage to the 
regulator may result in personal injury 
or property damage due to escaping of 
accumulated gas. To avoid such injury 
and damage, install the regulator in a 
safe location.
Under enclosed conditions or indoors, 
escaping gas may accumulate and be an 
explosion hazard. In this case, the vent 
should be piped outdoors.
For regulator constructions with a 
spring case vent, the vent should be 
kept open to permit free ow of gas 
to the atmosphere. Protect openings 
against entrance of rain, snow, insects 
or any other foreign material that may 
plug the spring case vent or vent line.
Before installing the regulator:
•  Unpack the regulator and remove the protective 
shipping plugs from the end connections of 
the body and the pressure connection in the 
spring case.
•  Check the regulator and make sure it has not 
been damaged or collected foreign material 
during shipping.
•  Remove any debris or dirt in the tubing and 
the pipeline.
•  Apply pipe compound to the external pipe thread 
for NPT bodies or use appropriate gaskets for 
anged bodies.
•  Make sure gas ow through the regulator is in the 
same direction as the arrow on the body.
On 1-1/2 or 2 in. / DN 40 or 50 Types MR95H, MR95HP 
and MR95HT regulators, the spring case vent is tapped 
so a vent line can be connected to provide venting to a 
remote location. On 1/4 NPT, 1/2, 3/4 and 1 in. / DN 15, 
20 and 25 Types MR95H, MR95HP and MR95HT body 
sizes, the tapped vent option is available on request. 
Protect the exposed end of the vent pipe with a weather 
and insect resistant vent assembly. Periodically check 
all vents and remote vent lines to ensure that they 
are unobstructed.
On Types MR95LD and MR95HD regulators, the 
loading pressure is connected to the 1/4 NPT 
connection in the spring case.
ATMOSPHERE
BLOCK
VALVE
(INLET) VENT
(OUTLET) VENT
TYPE 67CFR REGULATOR
PLANT AIR