MR95 Series
13
Types MR95L, MR95H, MR95HP 
and MR95HT
Key numbers are referenced in Figure 6, 8 or 9. 
1.  Loosen the jam nut (key 17).
2.  Turn the adjusting screw (key 15) clockwise to 
increase outlet pressure or counterclockwise to 
decrease it.
3.  Monitor the outlet pressure with a test gauge 
during the adjustment.
4.  Tighten the jam nut (key 17) to maintain the 
desired setting.
Types MR95LD and MR95HD
Key numbers are referenced in Figure 7 or 10. 
1.  Turn handwheel (key 38) clockwise to increase 
outlet pressure or counterclockwise to decrease it.
2.  Monitor the outlet pressure with a test gauge 
during the adjustment. 
Shutdown
1.  Close the upstream block valve to the regulator inlet.
2.  Close the downstream block valve to the 
regulator outlet.
3.  Vent the downstream pressure by slowly opening 
the bleed valve between the regulator and the 
downstream shutoff valve. Without changing 
regulator spring adjustment, all pressure between 
the upstream and downstream shutoff valves 
will be released through the bleed valve, since 
the Type MR95L, MR95H, MR95HP or MR95HT 
regulator opens in response to the decreased outlet 
pressure. For Types MR95L, MR95H, MR95HP 
and MR95HT regulators, skip steps 4, 5 and 6. For 
Types MR95LD and MR95HD continue steps 4 
through 6.
4.  Close the block valve to the loading pressure.
5.  Vent loading pressure slowly to release pressure 
in the spring case.
6.  Vent inlet pressure slowly (through the bleed 
valve) to release all remaining pressure in 
the regulator.
Maintenance
WARNING
!
To avoid personal injury, property damage 
or equipment damage caused by sudden 
release of pressure or explosion of 
accumulated gas, do not attempt any 
maintenance or disassembly without 
rst isolating the regulator from system 
pressure and relieving all internal 
pressure from the regulator.
To avoid possible personal injury from 
spring or pressure-loaded actuator, make 
certain the adjusting screw is completely 
backed off and the spring case pressure 
is vented prior to disassembly. Otherwise, 
the spring load or loading pressure could 
forcefully eject the spring case.
Regulators that have been disassembled 
for repair must be tested for proper 
operation before being returned to 
service. Only parts manufactured by 
Emerson™ should be used for repairing 
Fisher
®
 regulators.
Due to normal wear or damage that may 
occur from external sources, this regulator 
should be inspected and maintained 
periodically. The frequency of inspection 
and replacement of parts depends upon 
the severity of service conditions or the 
requirement of local, state and federal 
rules and regulations.
Due to normal wear that may occur, inspect the 
parts periodically and replace if necessary. The 
frequency of inspection depends on the severity of 
service conditions or the requirements of state and 
federal laws.
Replace parts such as the O-rings, gaskets, diaphragm 
and packing as necessary. Always apply lubricants as 
the regulator is being reassembled. Suitable lubricants 
are shown in the assembly drawings.
The regulator does not have to be taken out of the 
pipeline to be disassembled. All key numbers are 
referenced in Figures 4 to 10.