EasyManua.ls Logo

FläktGroup CET.ACEC - Installation of the FläktGroup CET.ACEC Compact Controller

FläktGroup CET.ACEC
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Assembly and Installation CET.ACEC compact controller
14 FläktGroup DC-2017-0104-GB 2018-05/R1 • Subject to change
3.3 Installation of the FläktGroup CET.ACEC compact controller
For the connection of the CET.ACEC compact controller we recommend the use of the
following cables or a comparable model.
The following steps are necessary to connect the CET.ACEC compact controller:
• Connecting mains electrical supply
• Connect HVAC equipment
• or connect status signals
• Connect external sensors, if required
• Connect Modbus interface, if required
3.3.1 Modbus Network
Fig. 3-1: Modbus Network
Connection type Terminal number Manufacturer Cable type Cross section
AC fan, valves 3,4,5,6,7,8 LAPP cable
ÖLFLEX® CLASSIC 110
1.5 mm
2
Fan EC (0-10V) 9.10 LAPP cable
ÖLFLEX® CLASSIC 110 CY
0.75 mm
2
Status signals 13,14,15,16 LAPP cable
ÖLFLEX® CLASSIC 110
0.75 mm
2
Sensor inputs 11,12,13 LAPP cable
ÖLFLEX® CLASSIC 110
0.75 mm
2
Modbus interface A,B LAPP cable
UNITRONIC® Li2YCYC TP
0.5 mm
2
NOTICE!
• f the Modbus network is longer than 100 meters, a 120 ? resistance should be
installed at the start and end of the bus. .
• The shielding of cables must be connected to at least one point on the PE
conductor.
• Also note the address setting described in Chapter „Set Modbus address“ on
page 22.
*