CET.ACEC compact controller Commissioning and testing
FläktGroup DC-2017-0104-GB 2018-05/R1 • Subject to change 17
4 Commissioning and testing
4.1 Factory settings
When the FläktGroup CET.ACEC compact controller is ordered together with an air-
handling unit, it is delivered pre-configured ex works. The configuration is harmonized
with the air-handling units.
4.2 Configuration of the FläktGroup CET.ACEC compact controller
Manual parameter settings
Only the first level parameters (number 1 to 11) can be adjusted with the compact con-
troller. The second level parameters (numbers 12 to 33) may only be changed with a
supervisor tool at the factory or with the Modbus on-site.
Fig. 4-4: Keys and LEDs used for the parameterization.
SEL 0
LED 1
LED 2
SEL 3
SEL 2
SEL 1
Electrocution through hazardous voltage will lead to death or serious injury.
The settings may only be executed by skilled electricians.
The covering must be removed from the compact controller before changing the
parameters.
In order to change the parameters, the compact controller must be energized.
Once the covering is opened, the electrically charged parts are accessible!