Flexfiller Digital Pressurisation Equipment
Flexfiller Models (125D, 225D, 150D, 250D, 280D)
Midi Models (125D, 225D, 150D, 250D)
Mini Models (130D, 230D)
Operation & Maintenance
Manual
Rev 8.3

Questions and Answers

  • M
    Michael WilsonAug 20, 2025
    What to do if LOW H20 fault is displayed on flamco Midi 225D?
    • D
      dixonrobertAug 20, 2025
      If the LOW H20 fault is displayed on your Flamco Portable Generator, here are a few things you can check: * Make sure the mains water supply to the unit is turned on. * The fault will clear once the break tank has been re-filled if the mains pressure is poor. * Remove any non-standard electrical connections from terminals 19 & 20. * Consider replacing the low water float switch, or the digital controller if they have failed.
  • J
    jgarciaAug 22, 2025
    Why pressure reading does not match actual system pressure on flamco Midi 225D?
    • S
      Susan Scott MDAug 22, 2025
      If the pressure reading on your Flamco Portable Generator doesn't match the actual system pressure, there might be a few reasons: * Ensure the internal isolation valve within the unit is open. * Review the SENSOR TYPE setting. * Remove any non-return valve installed between the unit and the system. * The pressure sensor might have failed and needs replacement.
  • M
    Matthew LopezAug 25, 2025
    What causes HIGH PRESSURE fault on Flamco Portable Generator?
    • K
      Kristen FranklinAug 25, 2025
      If your Flamco Portable Generator displays a HIGH PRESSURE fault, it could be due to a few reasons: * Check the expansion vessel pre-charge and re-charge if necessary. * Review the expansion vessel selection, as it might be undersized. * Review the system specifications, as the HIGH PRESSURE set point might be too low.
  • J
    Jennifer RodriguezAug 26, 2025
    How to fix pump that runs but does not make up pressure in flamco Midi 225D Portable Generator?
    • L
      lawrencebrentAug 26, 2025
      If your Flamco Portable Generator's pump runs but doesn't build up pressure, it might be air-locked. Try bleeding the pump to resolve this.
  • S
    Sean CooperAug 27, 2025
    What to do if system pressure has risen above the HIGH PRESSURE set point in flamco Midi 225D?
    • J
      James ReyesAug 27, 2025
      If the system pressure of your Flamco Portable Generator has risen above the HIGH PRESSURE set point, decrease the system pressure using a suitable drain point.
  • E
    Elizabeth GregoryAug 29, 2025
    What causes HIGH H20 fault on flamco Midi 225D Portable Generator?
    • L
      Lauren BoydAug 29, 2025
      If your Flamco Portable Generator displays a HIGH H20 fault, it could be due to: * A non-standard electrical connection into terminals 21 & 22. Remove any such connections. * A failure of the digital controller, which would require replacement.
  • A
    angela35Aug 31, 2025
    What to do if ERROR 1 fault is displayed on flamco Midi 225D Portable Generator?
    • S
      Shelly ShepherdAug 31, 2025
      If you see 'ERROR 1 fault' displayed on your Flamco Portable Generator, check the SENSOR TYPE option and review its setting. Also, the pressure sensor might have failed and require replacement.
  • K
    keith16Sep 2, 2025
    Why is the pump persistently becoming air-locked in flamco Midi 225D?
    • E
      Elizabeth BatesSep 2, 2025
      If your Flamco Portable Generator's pump is persistently becoming air-locked, check the float valve flow restrictor selection, especially if you have mini and midi units.
  • M
    Margaret PadillaSep 4, 2025
    Why is the break tank overfilling in Flamco Portable Generator?
    • M
      Martin CostaSep 4, 2025
      If the break tank in your Flamco Portable Generator is overfilling and discharging water, consider the following: * Check the float valve flow restrictor selection (mini and midi units only). * Set the float valve to its lowest possible position. * The float valve might have failed and needs replacement. * A pump non-return valve might have failed and needs replacement.
  • J
    Jason SchwartzSep 6, 2025
    Why is the pump repeatedly running in short bursts in flamco Midi 225D?
    • D
      David WhiteSep 6, 2025
      If your Flamco Portable Generator's pump is repeatedly running in short bursts, it could be due to: * The internal isolation valve within the unit being partially closed. Fully open it. * Too much restriction in the connecting pipe work. Increase bore, reduce bends, or reduce length. * A pump non-return valve has failed, replace it. * The expansion vessel has failed or lost its pre-charge, check and re-charge if necessary. * The unit's connection point is too far from the expansion vessel. Move them closer.

Summary

Equipment Overview

Installation

Installation Pipe Connections

Guidance on making correct pipe connections, including important warnings and requirements.

Electrical Power Supply Requirements

Details the requirements and safety precautions for connecting the unit to the electrical power supply.

Commissioning

Pre-Commissioning Checklist

Lists essential conditions to check before starting the commissioning process for safety and proper function.

Digital Controller Programming

Details how to access and modify controller settings using access codes and button operations.

Controller Program List

Details all menu items, their functions, and default values for controller configuration.

Hydraulic Commissioning Procedures

Guides on the hydraulic setup and initial operational steps for the unit.

Hydraulic Commissioning Procedures

Pump Bleeding Procedure

Procedure for bleeding air from the pumps, ensuring efficient operation and preventing damage.

Initial Start-up Procedure

Step-by-step guide for the initial start-up of the unit after hydraulic commissioning.

Unit Operation

Operation Fault Codes

Lists and explains all fault codes displayed on the digital controller and their reset methods.

Unit Maintenance

Wiring Diagram

Spare Parts Identification

Troubleshooting Guide

Troubleshooting: Pressure Faults

Solutions for 'LOW PRESSURE' and 'HIGH PRESSURE' faults and related problems.

Troubleshooting: Pump Limit and Failures

Addresses issues with pump flood limits, pump failures, and system undersizing.

Troubleshooting: Pump Type and Failures

Troubleshooting for incorrect pump type settings, pump failures, and isolation issues.

Troubleshooting: Controller Response and Power Issues

Troubleshooting controller response, parameter corruption, and power-up failures.