Rev 8.1 Aug-15 Page 1 / 44
Flexfiller Digital Pressurisation Equipment
Flexfiller Models (125D, 225D, 150D, 250D, 280D)
Midi Models (125D, 225D, 150D, 250D)
Mini Models (130D, 230D)
Operation & Maintenance
Manual
Rev 8.3

Questions and Answers

  • J
    Joshua RodgersAug 20, 2025
    What to do if LOW H20 fault is displayed on flamco Mini 130D Portable Generator?
    • A
      Anita PrattAug 20, 2025
      If the LOW H20 fault is displayed on your Flamco Portable Generator, here are a few things you can check: * Make sure the mains water supply to the unit is turned on. * The fault will clear once the break tank has been re-filled if the mains pressure is poor. * Remove any non-standard electrical connections from terminals 19 & 20. * Consider replacing the low water float switch, or the digital controller if they have failed.
  • B
    Brian LyonsAug 22, 2025
    Why pressure reading does not match actual system pressure on Flamco Portable Generator?
    • R
      rfernandezAug 22, 2025
      If the pressure reading on your Flamco Portable Generator doesn't match the actual system pressure, there might be a few reasons: * Ensure the internal isolation valve within the unit is open. * Review the SENSOR TYPE setting. * Remove any non-return valve installed between the unit and the system. * The pressure sensor might have failed and needs replacement.
  • D
    David BrayAug 25, 2025
    What causes HIGH PRESSURE fault on Flamco Portable Generator?
    • I
      idorseyAug 25, 2025
      If your Flamco Portable Generator displays a HIGH PRESSURE fault, it could be due to a few reasons: * Check the expansion vessel pre-charge and re-charge if necessary. * Review the expansion vessel selection, as it might be undersized. * Review the system specifications, as the HIGH PRESSURE set point might be too low.
  • D
    David DunnAug 26, 2025
    How to fix pump that runs but does not make up pressure in Flamco Portable Generator?
    • C
      coreythomasAug 26, 2025
      If your Flamco Portable Generator's pump runs but doesn't build up pressure, it might be air-locked. Try bleeding the pump to resolve this.
  • K
    Kelly WilsonAug 27, 2025
    What to do if system pressure has risen above the HIGH PRESSURE set point in flamco Mini 130D?
    • D
      Daniel ShawAug 28, 2025
      If the system pressure of your Flamco Portable Generator has risen above the HIGH PRESSURE set point, decrease the system pressure using a suitable drain point.
  • V
    vramirezAug 29, 2025
    What causes HIGH H20 fault on flamco Mini 130D Portable Generator?
    • T
      Theodore HaynesAug 29, 2025
      If your Flamco Portable Generator displays a HIGH H20 fault, it could be due to: * A non-standard electrical connection into terminals 21 & 22. Remove any such connections. * A failure of the digital controller, which would require replacement.
  • A
    Aaron HendersonAug 31, 2025
    What to do if ERROR 1 fault is displayed on flamco Mini 130D?
    • B
      Brenda SimsAug 31, 2025
      If you see 'ERROR 1 fault' displayed on your Flamco Portable Generator, check the SENSOR TYPE option and review its setting. Also, the pressure sensor might have failed and require replacement.
  • M
    michael55Sep 2, 2025
    Why is the pump persistently becoming air-locked in flamco Mini 130D Portable Generator?
    • C
      Cody TranSep 2, 2025
      If your Flamco Portable Generator's pump is persistently becoming air-locked, check the float valve flow restrictor selection, especially if you have mini and midi units.
  • K
    Kendra AvilaSep 4, 2025
    Why is the break tank overfilling in flamco Mini 130D?
    • C
      Cheryl JuarezSep 4, 2025
      If the break tank in your Flamco Portable Generator is overfilling and discharging water, consider the following: * Check the float valve flow restrictor selection (mini and midi units only). * Set the float valve to its lowest possible position. * The float valve might have failed and needs replacement. * A pump non-return valve might have failed and needs replacement.
  • S
    Shannon ClarkSep 6, 2025
    Why is the pump repeatedly running in short bursts in Flamco Portable Generator?
    • K
      Katelyn ChurchSep 6, 2025
      If your Flamco Portable Generator's pump is repeatedly running in short bursts, it could be due to: * The internal isolation valve within the unit being partially closed. Fully open it. * Too much restriction in the connecting pipe work. Increase bore, reduce bends, or reduce length. * A pump non-return valve has failed, replace it. * The expansion vessel has failed or lost its pre-charge, check and re-charge if necessary. * The unit's connection point is too far from the expansion vessel. Move them closer.

Summary

Commissioning Record

Installation

Flow Restrictor Installation

Electrical Power Supply Connection

Connection Requirements

Outlines how to connect the mains power supply safely and correctly.

Micro Controller Fault Contacts

Commissioning Process

Pre-Commissioning Checklist

Lists essential checks to perform before starting the commissioning process.

Controller Interface Overview

Controller Programming Menu

Accessing and Navigating Menus

Guides on entering codes and navigating through the controller's programming menu.

Controller Program Settings

Menu Item Descriptions

Details each menu item, its function, and default value.

Advanced Settings

Covers settings for experienced engineers like PUMP TYPE, SENSOR TYPE, CASCADE.

Hydraulic Commissioning

Bleeding Pumps Procedure

Procedure for bleeding air from the pumps.

Bleeding Pumps Details & Warnings

Shows bleed screw locations and warnings for bleeding pumps.

Forcing Pumps to Run

Explains how to manually run pumps for bleeding.

Unit Initial Start-up

Procedure and System Response

Details opening the isolation valve and how the unit responds to system pressure.

Unit Testing Procedure

Simulating a Minor Leak

Method for testing operation by slowly reducing system pressure.

Unit Operation Modes

Fault Codes

Lists and explains all fault codes displayed on the digital controller.

Shutdown & Start-up Procedures

Shutdown Procedure

Steps to safely shut down the pressurisation unit.

Routine Maintenance

Wiring Diagram

Wiring Location List

Spare Parts Identification

Flexfiller Model Parts

Midi Model Parts

Mini Model Parts

Troubleshooting

Low Pressure Faults

Solutions for 'LOW PRESSURE' displayed and pumps not running.

Pump Failures

Solutions for 'P1/P2 FAIL' and pump not making pressure.