19
NORDICPANEL
Code # A/B-alarm Name/text
1000–1999 Code range for – Hardware
1001 A B1 – Supply air temperature sensor fault
1002 B B6 – Exhaust air temperature sensor fault
1003 B B3 – Extract air temperature sensor fault
1004 A/B B4 – Outside air temperature sensor fault
1005 A B5 – Frost protection temp. Heating coil sensor fault.
1006 B H1 – Humidity sensor fault
1007 A/B RMC – Rotary heat exchanger motor stuck
1008 A/B RMC – Rotary heat exchanger belt broken
1009 A MI4 – Fire damper fault
1010 A/None TM1 – Supply air fan fault
1011 A/None TM2 – Exhaust air fan fault
1012 B 5RRPWHPSHUDWXUHVHQVRURQ&ΔIDXOW
1020 B 7LPHWRUHSODFHDLUȴOWHU
1021 Reserved
1022 B B10 – HWT top sensor fault
1023 B B11 – HWT middle sensor fault
1024 B B12 – Flow temp. heating circuit sensor fault
1025 B B13 – Return temp. heating circuit sensor fault
1026 B B14 – Flow temp. after reheating coil sensor fault
1027 B B15 – Return temp. HWT sensor fault
1028 B B16 – HWT bottom sensor fault
1029 A B20 – Frost protection temp. zone sensor fault
1030 B B21 – Supply air temperature sensor fault
1031 Reserved
1032 B P4 – Supply air pressure sensor fault
1033 B P5 – Extract air pressure sensor fault
1034 B 3Ȃ'LHUHQWLDOSUHVVXUHVXSSO\DLUVHQVRUIDXOW
1035 B 3Ȃ'LHUHQWLDOSUHVVXUHH[KDXVWDLUVHQVRUIDXOW
1036 A HWT all sensor fault
12345
67890
2.14. LOGIN SCREEN
To access the settings menus, you must log
LQbZLWKbDbFRGH
1000
To log in, enter the code 1000 and then press .