You should check manufacturers specification & conditions of used batteries before you input
Set V, Set A and Set Time for regeneration of batteries. Wrong set values will cause damage to
batteries due to over charge or other reasons.
2b. Program mode setup cont’d
1. Functional explanation of previous sample program:
a. MODE 1 Battery is discharged with a 74.8A load until either the
a
ctual voltage measures 30.6V (1.7Vpc 20%) or the timer reaches
10 hours. In effect Mode 1 is used to measure the beginning
battery capacity.
b. MODE 2 Start charging with 74.8A until measured voltage reaches
4
5V or 8 hour timer expires. Constant current, bulk charging
regeneration cycle.
c. MODE 3 Start charging with 37.4A until measured voltage equals
4
5V, when measured voltage equals 45V maintain set voltage until
8 hour timer expires by varying current. Constant voltage,
equalization cycle.
d. MODE 4 Second battery discharge with same parameters as mode
1
, the time it takes to complete this cycle can be directly compared
to the time it took to complete mode 1 cycle, showing any capacity
increase. (Mode 1 Time/ 8= original capacity %, Mode 2 Time/8 =
secondary capacity %)
e. MODE 5 Copy of mode 2 cycle. Fi
nal regeneration cycle
f. MODE 6 Copy of mode 3 cycle. Fi
nal equalization cycle.