EasyManua.ls Logo

FLOWMAX 170 - Technical Characteristics; Technical Data

FLOWMAX 170
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TECHNICAL CHARACTERISTCS
10
2. TECHNICAL CHARACTERISTICS
2.1 Technical data
Model
FLOWMAX 170
Heat Input max
kW - BTU/hr
51 - 174019
Heat Input min
kW - BTU/hr
12 – 40946
Heat Output max - 122/86°F
kW - BTU/hr
54.5 – 185859
Heat Output max - 167/140°F
kW - BTU/hr
49.9 – 170198
Heat Output min - 167/140°F
kW - BTU/hr
11.65 - 39758
Efficiency 100% (full load 167/140°F)
%
97.8
Central Heating circuit
Central Heating water temperature setting (min-max)
°C°F
30-75 / 25-40 86-167 / 77-104
Max. heating working temperature
°C°F
75/167
Expansion vessel capacity
gal
1.58
Max. working pressure (heating)
bar - psi
2.1 - 30
Min. working pressure (heating)
bar - psi
0.3 - 4.29
Domestic Hot Water circuit
D.H.W. temperature setting (min-max)
°C°F
35-60 95-140
Max. Hot water working pressure
bar - psi
6 - 86
Min. Hot water working pressure
bar - psi
0.5 - 7.16
D.H.W. flow rate at ∆T 45°F (25°C)
l/min - gal/min
30 - 7.93
D.H.W. flow rate at ∆T 72°F (40°C)
l/min - gal/min
18.8 4.95
Dimensions (Water heater casing size)
Width
in
19.3
Height
in
27.6
Depth
in
18.5
Weight (net)
lb
120
Hydraulic connections
Central Heating Flow connection
NPT
3/4"
Central heating Return connection
NPT
3/4"
Cold water mains connection
NPT
1/2"
D. Hot water connection
NPT
3/4"
Gas connection
NPT
3/4"
Gas Supply
Natural gas G 20
Inlet pressure
mbar - psi
20 - 0.29
Gas consumption
m
3
/h - ft
3
/h
5.40 190.7
Electrical specifications
Power supply
V/Hz
120/60
Electrical power consumption
W
225