INSTALLATION INSTRUCTIONS
39
4.5 Starting up the water heater
Once the system has been filled,
proceed as follows:
Check that the exhaust flue is free
of obstructions and correctly
connected to the water heater;
Switch on the power supply to the
water heater;
Open the gas isolation valve;
Place switch 1 in the ON position
(see 2.7 “Control Panel”), after a few
seconds the circulating pump will start
to run;
Use button 6 to set the SUMMER,
WINTER or SUMMER/WINTER
function. The symbols
will light
up (fixed light) to indicate that the
water heater is working;
The automatic ignition system will then
light the burner. This operation is
repeated for 3 times. It may however
be necessary to repeat the operation in
order to eliminate all the air from the
pipes. To repeat the operation, wait
approximately three minutes before re-
attempting to light the water heater. To
reset the water heater Switch off
switch 1 (see 2.7 “Control Panel”) and
switch it back on again and repeat the
lighting procedure;
With the water heater ignited, if the
system still emits noises, the
operations must be repeated until all
the air has been removed;
Check the pressure in the system. If
the pressure has fallen, re-open the
filling tap until the code H2O
disappears on the display and the
pressure reaches the middle of the
green area (1,2 bar). On completion,
close the filling tap.
If the CO2 value does not correspond to the specified value, adjust screw V (see fig. 1) on the venturi clockwise
to reduce the CO2 value or anticlockwise to increase it
;
Table n°1
Gas type
CO
2
%
Natural Gas - G20
9.3
Liquid Propane Gas - G 31
11
V
Fig. 1