EasyManua.ls Logo

FoxESS F5000-G2 - Page 16

FoxESS F5000-G2
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Grid Connection
This series inverters are designed for single-phase grid. Voltage range is 220/230/240V; frequency is
50/60Hz. Other technical requests should comply with the requirement of the local public grid.
Model (kW)
3.0
3.6
4.6
5.0
5.3*
6.0
Cable
4mm²
4mm²
6mm²
6mm²
6mm²
6mm²
Micro-Breaker
25A
25A
40A
40A
40A
40A
WARNING!
A micro-breaker for max output overcurrent protection device shall be installed between inverter and
grid, and the current of the protection device is referred to the table above, any load SHOULD NOT
be connected with the inverter directly.
Step 3: AC Wiring
Check the grid voltage and compare with the permitted voltage range (refer to technical data).
Disconnect the circuit-breaker from all the phases and secure against reconnection.
Trim the wires:
-
Trim all the wires to 52.5mm and the PE wire to 55mm.
-
Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
Separate the AC plug into three parts as below.
-
Hold middle part of the female insert, rotate the back shell to loosen it, and detach it from female inset.
-
Remove the cable nut (with rubber insert) from the back shell.
Slide the cable nut and then the back shell onto the cable.
L: Brown/Red Wire
N: Blue/Black Wire
PE: Yellow & Green Wire
Note: Please refer to local cable type and color for actual installation.

Related product manuals