7. Maintenance
This section contains information and procedures for solving possible problems with the FOXESS hybrid
inverters and provides you with troubleshooting tips to identify and solve most problems that can occur.
7.1 Alarm List
Item
Fault Code
Statement
Solution
1
1030
AC Overcurrent
The inverter will reconnect to the grid after the grid is
restored.
If the fault recurs, please contact FOXESS Customer
Service for further assistance.
2
1034
DC Component Current
Fault
Wait for the inverter to return to normal.
If the fault recurs, turn off the AC and DC side
switches, wait for 10 minutes, and then turn on the
AC and DC switches in turn to restart the inverter.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
3
1035
Leakage Overcurrent
Fault
The fault is caused by excessive parasitic
capacitance due to poor light or moist air. After the
environment improves, the inverter will reconnect to
the grid.
If the environment is normal, check whether the
insulation of the AC and DC cables is good.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
4
1036
Leakage Current Static
Fault
5
1040
Grid Voltage Imbalance
The inverter will reconnect to the grid after the grid is
restored.
If the fault recurs:
1. Check whether the protection parameter settings
meet the requirements through the APP.
2. Measure the actual grid voltage, confirm that the
grid voltage and frequency of each phase do not meet
the grid-tied requirements, and contact the local
power company for solutions.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
6
1042
Grid High Freq
7
1043
Grid Low Freq
8
1044
Grid Phase Volt
Over-limit
9
1045
Grid Line Volt Over-limit
10
1046
Inverting Current
Imbalance
11
1049
Capture PLL
Abnormality
12
1050
Inverting Hardware
Overcurrent
The inverter will reconnect to the grid after the grid is
restored.
If the fault recurs, please contact FOXESS Customer
Service for further assistance.