25
and DC switches in turn to restart the inverter.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
12V Auxiliary Power
Supply Fault
5V Auxiliary Power
Supply Fault
Check if the inverter is exposed to direct sunlight,
please shade the inverter properly.
Check and clean the air outlet.
Check whether there is a fan alarm through the APP
(refer to the solution to the fan alarm).
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
Inverting Current DC
Component Bias Fault
Wait for the inverter to return to normal.
If the fault recurs, turn off the AC and DC side
switches, wait for 10 minutes, and then turn on the AC
and DC switches in turn to restart the inverter.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
Inverting Current Bias
Fault
Inverting Soft Start
Time-out Fault
Freq Detection Value
Abnormality
The inverter will reconnect to the grid after the grid is
restored.
If the fault recurs:
1. Check whether the protection parameter settings
meet the requirements through the APP.
2. Measure the actual grid voltage, confirm that the
grid voltage and frequency of each phase do not meet
the grid-tied requirements, and contact the local
power company for solutions.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
Leakage CT Self-test
Fault
Wait for the inverter to return to normal.
If the fault recurs, turn off the AC and DC side
switches, wait for 10 minutes, and then turn on the AC
and DC switches in turn to restart the inverter.
If the fault still exists, please contact FOXESS
Customer Service for further assistance.
CPLD Program Version
Abnormality
Internal Control
Diagnose Fault
Check if the ground cables are connected properly.
Check if the insulation between the ground cable and
the live cable is good.
If the fault still exists, please contact FOXESS