EasyManua.ls Logo

Frick QUANTUM 1 - Vessel GCU Board Analog I;O Configuration

Frick QUANTUM 1
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FRICK QUANTUM™ CONDENSER/VESSEL CONTROL PANEL S90-555 M
MAINTENANCE Page 13
Vessel GCU Board Analog I/O Jumper Settings
Analog Input 1 -
V
essel Level #1
A
nalog Input 1 Sensor Wiring
Input Function JP8 JP9 Connector Function
0 – 5 VDC Out Out J4-10 +12 VDC
Resistance 1 - 2 Out J4-11 Input Signal
4 – 20 ma * Out * 1 – 2 * J4-12 GND
ICDT 2 - 3 Out
Analog Input 2 -
V
essel Level #2
A
nalog Input 2 Sensor Wiring
Input Function JP18 JP19 Connector Function
0 – 5 VDC Removed Removed J4-7 +12 VDC
Resistance 1 - 2 Removed J4-8 Input Signal
4 – 20 ma * Removed * 1 – 2 * J4-9 GND
ICDT 2 - 3 Removed
Analog Input 3 -
V
essel Level #3
A
nalog Input 3 Sensor Wiring
Input Function JP10 JP11 Connector Function
0 – 5 VDC Removed Removed J4-4 +12 VDC
Resistance 1 - 2 Removed J4-5 Input Signal
4 – 20 ma * Removed * 1 – 2 * J4-6 GND
ICDT 2 - 3 Removed
Analog Input 4 -
V
essel Pressure #1
A
nalog Input 4 Sensor Wiring
Input Function JP20 JP21 Connector Function
0 – 5 VDC * Removed * Removed * J4-1 +12 VDC
Resistance 1 - 2 Removed J4-2 Input Signal
4 – 20 ma Removed 1 – 2 J4-3 GND
ICDT 2 - 3 Removed
Analog Input 5 -
V
essel Pressure #2
A
nalog Input 5 Sensor Wiring
Input Function JP12 JP13 Connector Function
0 – 5 VDC * Removed * Removed * J5-10 +12 VDC
Resistance 1 - 2 Removed J5-11 Input Signal
4 – 20 ma Removed 1 – 2 J5-12 GND
ICDT 2 - 3 Removed
Analog Input 6 -
V
essel Pressure #3
A
nalog Input 6 Sensor Wiring
Input Function JP22 JP23 Connector Function
0 – 5 VDC * Removed * Removed * J5-7 +12 VDC
Resistance 1 - 2 Removed J5-8 Input Signal
4 – 20 ma Removed 1 – 2 J5-9 GND
ICDT 2 - 3 Removed
Analog Input 7 - Refrigeration Pump Pressure #1
A
nalog Input 7 Sensor Wiring
Input Function JP14 JP15 Connector Function
0 – 5 VDC * Removed * Removed * J5-4 +12 VDC
Resistance 1 - 2 Removed J5-5 Input Signal
4 – 20 ma Removed 1 – 2 J5-6 GND
ICDT 2 - 3 Removed
Analog Input 8 - Refrigeration Pump Pressure #2
A
nalog Input 8 Sensor Wiring
Input Function JP24 JP25 Connector Function
0 – 5 VDC * Removed * Removed * J5-1 +12 VDC
Resistance 1 - 2 Removed J5-2 Input Signal
4 – 20 ma Removed 1 – 2 J5-3 GND
ICDT 2 - 3 Removed

Related product manuals