S90-555 M FRICK QUANTUM™ CONDENSER/VESSEL CONTROL PANEL
Page 14 MAINTENANCE
Vessel GCU Board Analog I/O Jumper Settings (Continued)
Analog Input 9 - Refrigeration Pump Pressure #3
A
nalog Input 9 Sensor Wiring
Input Function JP16 JP17 Connector Function
0 – 5 VDC * Removed * Removed * J11-7 +12 VDC
Resistance 1 - 2 Removed J11-8 Input Signal
4 – 20 ma Removed 1 – 2 J11-9 GND
ICDT 2 - 3 Removed
Analog Input 10 - Analog Auxiliary 1
A
nalog Input 10 Sensor Wiring
Input Function JP26 JP27 Connector Function
0 – 5 VDC * Removed * Removed * J11-4 +12 VDC
Resistance 1 - 2 Removed J11-5 Input Signal
4 – 20 ma Removed 1 – 2 J11-6 GND
ICDT 2 - 3 Removed
Analog Input 11 - Analog Auxiliary 1
A
nalog Input 11 Sensor Wiring
Input Function JP6 JP7 Connector Function
0 – 5 VDC * Removed * Removed * J11-1 +12 VDC
Resistance 1 - 2 Removed J11-2 Input Signal
4 – 20 ma Removed 1 – 2 J11-3 GND
ICDT 2 - 3 Removed
Analog Output Configurations
Analog Output 1 Sensor Wiring -
Vessel #1 Modulating Valve
Analog Output 2 Sensor Wiring -
Vessel #2 Modulating Valve
Connector Function Connector Function
J8-8 Output Signal J8-6 Output Signal
J8-7 GND J8-5 GND
Analog Output 3 Sensor Wiring -
Vessel #3 Modulating Valve
Analog Output 4 Sensor Wiring -
Future
Connector Function Connector Function
J8-4 Output Signal J8-2 Output Signal
J8-3 GND J8-1 GND
Condenser GCU Board Analog I/O Jumper Settings