SECTION 8
TROUBLESHOOTING
TROUBLESHOOTING A PROBLEM THAT APPEARS
UNEXPLAINABLE
When there is a problem that makes no sense due to
unexplainable things happening, check the following:
1. Is the panel powered by an isolating power source
such as a control transformer?
2. Is the panel powered from a lighting or utility panel?
3. Has the unit ever worked properly?
4. If the unit used to work properly, try to determine
when the problem rst showed up.
5. It is important to know if the problem occurs
randomly, frequently, or all the time.
6. Check what the temperature is at the unit location. Is
it very hot or very cold?
Make sure that a motor is not blowing exhaust air
on the control panel.
7. If it just started to act up, then check if there was
recently a severe lightning storm, re, ood, or a
plant accident. If any of the following conditions are
possible, then check for it:
Has any water, refrigerant, or oil leaked into the
panel or conduit?
8. If it just started to act up, then check if anything
was recently changed in the system (i.e. software or
hardware.)
9. If it just started to act up, then check if any service
was recently done to the unit or its electrical system?
10. If there is communication wiring connecting the panel
to another panel or device, then check the following:
If the Quantum™ is unexplainably shutting down,
try disconnecting the communications cable to see
if the problem goes away.
Check if the communications cable shields are
tied to machine ground at only one location. For
a PLC or Opto22 based system, the shield should
normally be tied only at the PLC or Opto22 panel.
Check that you are using the Frick® recommended
communications cable. See manual to match
proper cable with type of communications (i.e.,
RS-422, RS-232, RS-485, or some other type of
factory communication bus system.)
10. If this is an older plant, has the plant wiring been
brought up to code?
11. Is power wiring mixed with control wiring?
12. Is power wiring mixed with sensor wiring?
13. Is power wiring mixed with communications wiring?
14. Ensure that pressure transducers are properly
grounded. The two types of transducers you may
have are as follows: an older type has an 8 to 10 inch
3-conductor pigtail coming out of the transducer.
This type will have the attaching cable’s shield cut
off and insulated at the transducer end. The shield
is then tied to a panel ground terminal in the panel.
The newer type has the cable as an integral part of
the housing and has the shield crimped to the case
at the transducer end. This type of transducer has
the cable’s shield cut off and insulated in the control
panel.
15. Ensure that temperature transducers are properly
grounded. The temperature probes usually have two
short wires coming out of the sensor, and are tied to
a shielded cable at the thermal well head. The shield
is insulated at the temperature probe and grounded
at the panel end.
16. Check if one of the temperature probes has a signal
wire shorted to machine ground. To do this, rst pull
the orange plug from the appropriate channel of the
Analog board and then use a DVM and check each
white wire to machine ground and each black wire to
machine ground.
17. Check that all inductive loads (i.e. Coils, Solenoids,
or Relays, etc.) connected to the I/O output modules
have surge suppressers across them, preferably at
the devices and not at the panel end.
18. Make sure that you have a continuous ground back
to the power source. The ground connection must be
aluminum or copper. A conduit ground will not work.
19. Ensure that there is no AC wiring lying next to any
printed circuit boards.
20. Unexplainable unit failures are usually indicative
of noise due to wiring problems (i.e. incorrect
earth grounds, mixed power and control wiring,
unsuppressed coils, etc)
21. If the unit is unexplainably shutting down, check if the
machine shares power with something else.