Installation and Maintenance
6HUYLFH0DQXDO
%DODQFH5HIULJHUDQWRIWKHZD\9DOYH
*DVOHDNDJH
3URFHGXUH
&RQ¿UPWKDWERWKWKHZD\DQGZD\YDOYHVDUHVHWWR
WKHEDFNVHDW
&RQQHFWWKHFKDUJHVHWWRWKHZD\YDOYHVSRUW
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
 2SHQWKHYDOYH/R VLGHRQWKHFKDUJH VHWDQGGLV
FKDUJHWKHUHIULJHUDQWXQWLOWKHJDXJHLQGLFDWHVNJFP
*
– If there is no air in the refrigerant cycle (the pressure when the
air conditioner is not running is higher than 1kg/cm
2
G),
discharge the refrigerant until the gauge indicates 0.5 to
1kg/cm
2
G. if this is the case, it will not be necessary to apply
a evacuation.
– Discharge the refrigerant gradually; if it is discharged too
suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way
valve
3-Way
valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit