Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during opration.
4. Acceptable operating voltage: 187V-253V
Model Name MC12Y3JM MC18Y3JM
Power Supply V, Ø, Hz 208/230, 1, 60
208/230, 1, 60
Capacity
Cooling Nominal Btu/h 12,000
18,000
Heating Nominal Btu/h 13,800
20,800
Casing Color - -
-
Dimensions Body
W x H x D mm 570 × 214 × 570
570 × 256 × 570
W x H x D inch 22-7/16 x 8-7/16 x 22-7/16
22-7/16 x 10-3/32 x 22-7/16
Net Weight Body kg (lbs) 14.0 (30.9)
15.0 (33.1)
Heat Exchanger
(Row x Column x Fins per inch) x No.
- (2 x 8 x 18) x 1 (2 x 10 x 18) x 1
Face Area
m
2
(ft
2
) 0.22 (2.40) 0.28 (3.00)
Fan
Type - Turbo Fan
Turbo Fan
Air Flow Rate
H / M / L CMM 9.5 / 8.0 / 7.0
13.0 / 12.0 / 11.0
H / M / L CFM 335 / 283 / 247
459 / 424 / 388
Fan Motor
Type - BLDC
BLDC
Output W x No. 43 x 1
43 x 1
Running Current A 0.25
0.25
Sound Pressure Level H / M / L dB(A) 38 / 35 / 32
38 / 37 / 34
Piping
Connections
Liquid mm(inch) 6.35 (1/4)
6.35 (1/4)
Gas mm(inch) 9.52 (3/8)
12.7 (1/2)
Drain (O.D. / I.D.) mm(inch) 32.0(1-1/4) / 25.0(1)
32.0(1-1/4) / 25.0(1)
Safety Devices
-Fuse
Fuse
- Thermal Protector for Fan Motor
Thermal Protector for Fan Motor
Power and Communication Cable (included Earth)
No. x AWG 4C x 14 / 18 4C x 14 / 18
Decoration
Panel
(Accessory)
Model Name - DCG1218
DCG1218
Dimensions
W x H x D mm 700 x 22 x 700
700 x 22 x 700
W x H x D inch 27-9/16 x 7/8 x 27-9/16
27-9/16 x 7/8 x 27-9/16
Net weight kg (lbs) 3.0 (6.6)
3.0 (6.6)