Service Manual
95992013_00
Single Package Vertical Heat Pump System
R-410A Refrigerant
THE EXPERTS IN ROOM AIR CONDITIONING
VHA - 18K25RTQ, 18K34RTQ, 18K50RTQ, 18K75RTQ
VHA - 18R25RTQ, 18R34RTQ, 18R50RTQ, 18R75RTQ
18K
24K
VHA - 24K25RTQ, 24K34RTQ, 24K50RTQ, 24K75RTQ, 24K10RTQ
VHA - 24R25RTQ, 24R34RTQ, 24R50RTQ, 24R75RTQ, 24R10RTQ
VHA - 09K25RTQ, 09K34RTQ, 09K50RTQ
VHA - 09R25RTQ, 09R34RTQ, 09R50RTQ
9K
12K
VHA - 12K25RTQ, 12K34RTQ, 12K50RTQ
VHA - 12R25RTQ, 12R34RTQ, 12R50RTQ

Table of Contents

Questions and Answers

  • A
    Amanda HarrellAug 6, 2025
    What to do if the high pressure switch is open on my Friedrich Heat Pump?
    • D
      Darlene AliAug 6, 2025
      If the high pressure switch is open in your Friedrich Heat Pump, it could be due to a faulty pressure switch or the discharge pressure being too high. Check the connection points and confirm system pressures and operation. If operating in cooling mode, ensure the outdoor condensing fan motor is running.
  • J
    Joshua FosterAug 10, 2025
    What causes a high pressure switch lockout in a Friedrich VERT-I-PAK VHA24K50RTQ Heat Pump?
    • C
      Charles HernandezAug 11, 2025
      If the high pressure switch lockout occurs on your Friedrich Heat Pump, it could be caused by a faulty pressure switch or excessively high discharge pressure. Begin by checking the connection points. Next, verify the system pressures and overall operation, taking corrective measures as necessary. If the unit is in cooling mode, ensure that the outdoor condensing fan motor is functioning correctly.
  • B
    Brenda MorganAug 14, 2025
    Why is the low pressure switch open on my Friedrich VERT-I-PAK VHA24K50RTQ?
    • S
      sandrewsAug 14, 2025
      If the low pressure switch is open on your Friedrich Heat Pump, it could be due to a faulty pressure switch or the suction line pressure being too low. Check the connection points and confirm system pressures and operation, addressing any issues found. Also, if in cooling mode, ensure the indoor blower is running.
  • C
    Christopher WrightAug 18, 2025
    What does it mean when the low pressure switch lockout occurs on a Friedrich VERT-I-PAK VHA24K50RTQ Heat Pump?
    • M
      mccallkennethAug 18, 2025
      If a low pressure switch lockout occurs with your Friedrich Heat Pump, the possible cause is a faulty pressure switch or suction line pressure that is too low. Start by confirming the connection points. Then, check the system pressures and operation, and address any issues. If the unit is cooling, verify that the indoor blower is running.
  • A
    anthonymathisAug 23, 2025
    How to fix a coil sensor failure on a Friedrich VERT-I-PAK VHA24K50RTQ Heat Pump?
    • K
      Kelly ValenzuelaAug 23, 2025
      If your Friedrich Heat Pump displays a coil sensor failure, it means an open or shorted sensor has been detected. First, check the connection points. Then, use an ohmmeter to test the sensor to see if it's open (OL) or shorted (0.0 Ohms). If the sensor tests ok, replace the board. Refer to Appendix 1 (Thermistor resistor values).
  • M
    Margaret McguireAug 27, 2025
    What causes an ambient sensor failure in a Friedrich VERT-I-PAK VHA24K50RTQ Heat Pump?
    • S
      Savannah FloresAug 27, 2025
      If your Friedrich Heat Pump is showing an ambient sensor failure, this indicates that an open or shorted sensor has been detected. Begin by checking all connection points. Next, use an ohmmeter to check the sensor for an open (OL) or shorted (0.0 Ohms) circuit. If the sensor appears to be functioning correctly, the next step is to replace the board. For reference, see Appendix 1 (Thermistor resistor values).
  • N
    Nicholas ColonSep 1, 2025
    How to troubleshoot a Friedrich VERT-I-PAK VHA24K50RTQ with a control fault (no power)?
    • G
      gina16Sep 1, 2025
      If your Friedrich Heat Pump is experiencing a control fault and has no power, confirm the incoming voltage. If voltage is present, replace the board.

Summary

INTRODUCTION AND EQUIPMENT IDENTIFICATION

Safety Information and Hazards

General safety guidelines, personal injury, electrical, and property damage hazards.

SPECIFICATIONS AND INSTALLATION

Electrical and General Specifications

Detailed specs for electrical, capacities, efficiencies, and voltages.

OPERATION AND CONTROL

Sequence of Operation and Defrost

Unit operation sequence, pressure switches, defrost modes, and control board.

TROUBLESHOOTING AND COMPONENT IDENTIFICATION

Control Diagnostic Modes

Explains control diagnostic modes indicated by LEDs for troubleshooting.

COMPONENT TESTING AND REPAIR

Compressor Checks and Efficiency

Procedures for checking compressor voltage, amperage, resistance, and efficiency.

R-410 A SEALED SYSTEM REPAIR

System Considerations and Charging

R-410A system requirements, equipment, charging methods, and charge issues.

Component Replacement Procedures

Step-by-step instructions for replacing compressor, valve, and TXV.

Friedrich VERT-I-PAK VHA24K50RTQ Specifications

General IconGeneral
ModelVHA24K50RTQ
Cooling Capacity (BTU/h)24000
Heating Capacity (BTU/h)24000
Heating Seasonal Performance Factor (HSPF)8.2
RefrigerantR-410A
Voltage (V)208/230
Phase1
Compressor TypeRotary
Frequency (Hz)60
TypeHeat Pump