EasyManua.ls Logo

Friedrich WallMaster WCT16 - Troubleshooting; Troubleshooting Tips

Friedrich WallMaster WCT16
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
M. TROUBLESHOOTING
M.1. Troubleshooting Tips
COMPLAINT CAUSE SOLUTION
Unit does not operate.
The unit is turned to the off position, or the
thermostat is satised.
Turn the unit to the on position and raise or lower temperature
setting (as appropriate) to call for operation.
The LCDI power cord is unplugged.
Plug into a properly grounded 3 prong receptacle. See “Electrical
Rating Tables” on Page 6 for the proper receptacle type for your
unit.
The LCDI power cord has tripped (Reset
button has popped out).
Press and release RESET (Listen for click. Reset button latches
and remains in.) to resume operation.
The circuit breaker has tripped or the
supply circuit fuse has blown.
Reset the circuit breaker, or replace the fuse as applicable. If
the problem continues, contact a licensed electrician.
There has been a local power failure.
The unit will resume normal operation once power has been
restored.
Unit Trips Circuit Breaker or
Blows Fuses.
Other appliances are being used on the
same circuit.
The unit requires a dedicated outlet circuit, not shared with other
appliances.
An extension cord is being used.
Do NOT use an extension cord with this or any other air condition-
er.
The circuit breaker or time-delay fuse is
not of the proper rating.
Replace with a circuit breaker or time-delay fuse of the proper
rating. See Table E.1 for the proper circuit breaker/ fuse rating for
your unit. If the problem continues, contact a licensed electrician.
LCDI Power Cord Trips
(Reset Button Pops Out).
The LCDI power cord can trip (Reset
button pops out) due to disturbances on
your power supply line.
Press and release RESET (Listen for click. Reset button latches
and remains in.) to resume normal operation.
Electrical overload, overheating, or cord
pinching can trip (Reset button pops out)
the LCDI power cord.
Once the problem has been determined and corrected, press
and release RESET (Listen for click. Reset button latches
and remains in.) to resume normal operation.
NOTE: A damaged power supply cord must be replaced with a new power supply cord obtained from the product manu-
facturer and must not be repaired. The power cord must be replaced by trained service personnel.
Unit Does Not Cool/ Heat Room
Sufciently, or Cycles On And Off
Too Frequently.
The return/ discharge air grille is blocked.
Ensure that the return and/ or discharge air paths are not blocked
by curtains, blinds, furniture, etc.
Windows or doors to the outside are open. Ensure that all windows and doors are closed.
The temperature is not set at a cool
enough/ warm enough setting.
Adjust the Temperature control to a cooler or warmer setting as
necessary.
The lter is dirty or obstructed. Clean the lter, (see Routine Maintenance), or remove obstruction.
The indoor coil or outdoor coil is dirty or
obstructed.
Clean the coils, (see Routine Maintenance), or remove obstruction.
There is excessive heat or moisture
(cooking, showers, etc.) in the room.
Be sure to use exhaust vent fans while cooking or bathing and,
if possible, try not to use heat producing appliances during the
hottest part of the day.
The temperature of the room you are
trying to cool is extremely hot.
Allow additional time for the air conditioner to cool off a very hot
room.

Related product manuals