Do not install the inverter on a vertical wall or pillar with its con-
nection sockets facing upwards.
Do not install the inverter overhanging with the connection sock-
ets at the top.
Do not install the inverter overhanging with the connection sock-
ets at the bottom.
Do not install the inverter on the ceiling.
General com-
ments regarding
choice of loca-
tion
Please note the following criteria when choosing a location for the inverter:
Install only on a solid, non-flammable surface
Max. ambient temperatures:
-40 °C / +60 °C
Relative humidity:
0-100%
The airflow within the inverter is
from the right to the top (cold air
taken in from the right, hot air dis-
sipated out of the top).
The exhaust air can reach a temper-
ature of 70 °C.
If the inverter is installed in a switch cabinet or a similar sealed area, then
forced-air ventilation must be provided to ensure adequate heat dissipation.
If the inverter is to be installed on the outer wall of a cattle shed, maintain a
minimum all-round clearance of 2 m between the inverter and all ventilation
and other openings in the building.
The installation location must not be exposed to ammonia, corrosive vapours,
salts or acids.
9
EN