EasyManua.ls Logo

Fronius IG 4000 - Fronius IG 4500-LV Technical Data

Fronius IG 4000
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
105
EN-US
Fronius IG 4500-
LV
Input data
Output data
* Valid to 104 °F (40 °C) when DC operating voltage is above 200 V
** assured by electrical design of the inverter
Recommended PV power 3600 -5500 Wp
MPP voltage range 150 - 400 V DC
Max. input voltage
(at 1000 W/m² / 14 °C in an open circuit)
500 V DC
Nominal input voltage 280 V
Nominal input current 18.3 A
Max. input current 29.3 A
Max. array short circuit current 40 A
Nominal output power (P
nom
) 4500 W *
P
nom
at +122 °F (50 °C) 4200 W
Max. output power 4500 W
Nominal AC output voltage 208 V
Grid voltage tolerance +10 / -12 %
Operating AC voltage range default, 183 - 229 V
Adjustment range for voltage, 180 - 240 V
Voltage trip limit accuracy ± 1.5 % of nominal value
Nominal output current 21.6 A AC
Number of phases 1
Maximum continuous utility backfeed current ** 0 A
Synchronization in-rush current ** 0 A
Maximum output fault current / duration 21.6 A / 60 ms
Nominal output frequency 30 A
Operating frequency range 60 Hz
Adjustment range for frequency 59.3 - 60.5 Hz
Frequency trip limit accuracy 57.0 - 60.5 Hz
Frequency clearing times ± 0.02 Hz
Harmonic distortion < 5 %
Power factor
(at nominal output power)
1

Table of Contents